7-2 Magnetic Contactor / Air Circuit Breaker and Non-fuse Circuit Breaker

Magnetic Contactor (MC) and Air Circuit Breaker (ACB)
It is recommended the surrounding temperature for MC should be ≥ 60°C and that for ACB should be
≥ 50°C. In the meanwhile, consider temperature derating for components with ON/OFF switch in
accordance with the ambient temperature of the on-site distribution panel.
230V Series
Frame
A
B
C
VFD370CP23A-00/21
D
VFD450CP23A-00/21
VFD550CP23A-00/21
E
VFD750CP23A-00/21
VFD900CP23A-00/21
460V Series
Frame
A
B
C
Model
VFD007CP23A
VFD015CP23A
VFD022CP23A
VFD037CP23A
VFD055CP23A
VFD075CP23A
VFD110CP23A
VFD150CP23A
VFD185CP23A
VFD220CP23A
VFD300CP23A
Model
VFD007CP43A-21
VFD015CP43B-21
VFD022CP43B-21
VFD037CP43B-21
VFD040CP43A-21
VFD055CP43B-21
VFD075CP43B-21
VFD110CP43B-21
VFD150CP43B-21
VFD185CP43B-21
VFD220CP43A-21
VFD300CP43B-21
VFD370CP43B-21
Chapter 7 Optional AccessoriesCP2000
Light duty output
Light duty input current
current [A]
5
7.5
10
15
21
31
46
61
75
90
105
146
180
215
276
322
Light duty output
Light duty input current
current [A]
3.0
4.2
5.5
8.5
10.5
13
18
24
32
38
45
60
73
7-7
MC/ACB selection
[A]
[A]
6.4
11
9.6
18
15
22
22
40
25
40
34
55
51
85
67
105
83
130
99
150
116
185
146
225
180
265
215
330
276
400
322
500
MC/ACB selection
[A]
[A]
4.3
7
6.0
9
8.1
12
12.4
22
16
32
20
32
22
40
26
40
35
55
42
65
50
75
66
105
80
130
Table 7-7