Non-Fuse Circuit Breaker Chart; Fuse Specification Chart - Delta VFD-VL Series User Manual

Elevator drive
Table of Contents

Advertisement

Call 1(800)985-6929 for Sales
B.2 Non-fuse Circuit Breaker Chart
Comply with UL standard: Per UL 508, paragraph 45.8.4, part a,
The current rating of the breaker shall be within 2-4 times maximum input current rating.
Model
VFD055VL23A
VFD055VL43A
VFD075VL23A
VFD075VL43A
VFD110VL23A
VFD110VL43A
VFD150VL23A
VFD150VL43A
VFD185VL23A
VFD185VL43A
B.3 Fuse Specification Chart
Smaller fuses than those shown in the table are permitted.
Model
VFD055VL23A
VFD055VL43A
VFD075VL23A
VFD075VL43A
VFD110VL23A
VFD110VL43A
VFD150VL23A
VFD150VL43A
VFD185VL23A
VFD185VL43A
VFD220VL23A
VFD220VL43A
Call 1(800)985-6929 for Sales
deltaacdrives.com
3-phase
Recommended Input
Current (A)
50
30
60
40
100
50
125
60
150
75
I (A)
Input
26
14
34
19
50
25
60
32
75
39
90
49
deltaacdrives.com
sales@deltaacdrives.com
Appendix B Accessories|
Model
VFD220VL23A
VFD220VL43A
VFD300VL23A
VFD300VL43A
VFD370VL23A
VFD370VL43A
VFD450VL43A
VFD550VL43A
VFD750VL43A
I (A)
Output
I (A)
25
50
13
30
33
60
18
40
49
100
24
50
65
125
32
60
75
150
38
75
90
175
45
100
B-9
sales@deltaacdrives.com
VFD-VL
Recommended Input
Current (A)
175
100
225
125
250
150
175
250
300
Line Fuse
Bussmann P/N
JJN-50
JJN-30
JJN-60
JJN-40
JJN-100
JJN-50
JJN-125
JJN-60
JJN-150
JJN-70
JJN-175
JJN-100

Hide quick links:

Advertisement

Table of Contents
loading