Magnetic Contactor / Air Circuit Breaker And Non-Fuse Circuit Breaker - Delta C2000 Plus Series User Manual

High performance vector control drive
Table of Contents

Advertisement

7-2 Magnetic Contactor / Air Circuit Breaker and Non-fuse Circuit Breaker

Magnetic Contactor (MC) and Air Circuit Breaker (ACB)
It is recommended the surrounding temperature for MC should be ≥ 60°C and that for ACB should be ≥
50°C. In the meanwhile, consider temperature derating for components with ON/OFF switch in accordance
with the ambient temperature of the on-site distribution panel.
230V models
Frame
VFD007C23A-21
VFD015C23A-21
A
VFD022C23A-21
VFD037C23A-21
VFD055C23A-21
B
VFD075C23A-21
VFD110C23A-21
VFD150C23A-21
C
VFD185C23A-21
VFD220C23A-21
VFD300C23A-00
VFD300C23A-21
D
VFD370C23A-00
VFD370C23A-21
VFD450C23A-00
VFD450C23A-21
VFD550C23A-00
E
VFD550C23A-21
VFD750C23A-00
VFD750C23A-21
VFD900C23A-00
F
VFD900C23A-21
460V models
Frame
VFD007C43A-21
VFD015C43A-21
VFD022C43A-21
A
VFD037C43A-21
VFD040C43A-21
VFD055C43A-21
VFD075C43A-21
B
VFD110C43A-21
VFD150C43A-21
Model
Output Current (A)
Model
Output Current (A)
Chapter 7 Optional AccessoriesC2000 Plus
Heavy Duty
Heavy Duty
Input Current (A)
5
8
11
17
25
33
49
65
75
90
120
146
180
215
255
346
Heavy Duty
Heavy Duty
Input Current (A)
3
4
6
9
10.5
12
18
24
32
7-9
MC/ACB
Selection (A)
6.4
11
12
22
16
32
20
32
28
55
36
65
52
85
72
130
83
150
99
150
124
185
143
225
171
265
206
330
245
400
331
500
MC/ACB
Selection (A)
4.3
5.9
8.7
18
14
22
15.5
32
17
32
20
32
26
40
35
55
Table 7-7
7
9

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Vfd007c23a-21Vfd007c43a-21Vfd007c4ea-21Vfd015c23a-21Vfd015c43a-21Vfd015c4ea-21 ... Show all

Table of Contents