ABB ADVAC 03 Installation & Maintenance Instructions Manual
ABB ADVAC 03 Installation & Maintenance Instructions Manual

ABB ADVAC 03 Installation & Maintenance Instructions Manual

Medium voltage vacuum power circuit breakers and auxiliary

Advertisement

IB 6.2.15.7-1C
ABB IB 6.2.15.7-1C
1
November 2005
TM
ADVAC
Model 03 Medium Voltage
Vacuum Power Circuit Breakers and Auxiliary
Installation/Maintenance Instructions

Advertisement

Table of Contents
loading

Summary of Contents for ABB ADVAC 03

  • Page 1 IB 6.2.15.7-1C ABB IB 6.2.15.7-1C November 2005 ADVAC Model 03 Medium Voltage Vacuum Power Circuit Breakers and Auxiliary Installation/Maintenance Instructions...
  • Page 2: Table Of Contents

    ABB IB 6.2.15.7-1C ABLE OF ONTENTS FORWARD ................................3 INTRODUCTION & SAFE PRACTICES ........................4 Introduction ..............................4 Safe Practices .............................. 4 RECEIVING, HANDLING, & STORAGE ........................5 Receiving ..............................5 Handling ............................... 5 Storage ................................. 5 INSERTION AND REMOVAL ........................... 6 Insertion ................................
  • Page 3: Forward

    ABB IB 6.2.15.7-1C FORWARD This booklet provides information for the ADVAC breakers as described below. Not all sections of the bulletin apply to all types of ADVAC circuit breakers. For example, the racking and interlock sections do not apply to the fixed mount breaker styles.
  • Page 4: Introduction & Safe Practices

    ABB IB 6.2.15.7-1C INTRODUCTION & SAFE PRACTICES NTRODUCTION The purpose of this manual is to provide instructions for unpacking, storage, installation, operation and maintenance for the ADVAC™ vacuum circuit breakers. This manual should be carefully read and used as a guide during installation, initial operation, and maintenance.
  • Page 5: Receiving, Handling, & Storage

    If damage or indication of rough handling is evident, file a damage claim at once with the carrier and promptly notify the nearest District Office. ABB is not responsible for damage of goods after delivery to the carrier.
  • Page 6: Insertion And Removal

    ABB IB 6.2.15.7-1C INSERTION AND REMOVAL NSERTION AND EMOVAL This section describes the process for inserting the breaker into the disconnect position of the switchgear and the removal of the circuit breaker from the disconnect position. Racking of the circuit breaker to and from the test and disconnect position is covered in the following section.
  • Page 7: Racking

    ABB IB 6.2.15.7-1C INSERTION AND REMOVAL ACKING ADVAC™ circuit breakers are designed with three positive racking positions. The Disconnect position allows only manual operation of the breaker without control power and with the shutters closed. The Test Position allows manual and electrical operation of the breaker with control power supplied through the secondary contacts with the shutters closed.
  • Page 8 ABB IB 6.2.15.7-1C INSERTION AND REMOVAL HROUGH ISCONNECT 1. Perform visual inspection: a. Verify Close/Open Indicator shows OPEN b. Verify switchgear Door is CLOSED. 2. Actuate (push down) Position Release Lever (9) to begin racking from Test position a. Begin racking in the COUNTER-CLOCKWISE direction b.
  • Page 9: Mechanism And Operation

    ABB IB 6.2.15.7-1C MECHANISM AND OPERATION ECHANISM AND PERATION (Refer to Fig. 2A And 2B) The ADVAC™ medium voltage circuit breaker uses a spring for stored energy. The Closing Spring (11) is a toroidal spring. This spring supplies the energy necessary to close the breaker and assists with the opening. During the closing operation, Opening Springs (6) (compression type) are charged along with Contact Springs (4) (also compression type) in the pole assembly.
  • Page 10 ABB IB 6.2.15.7-1C MECHANISM AND ASSEMBLED POLE 1a Upper contact terminal Kabelabgangsfeld 1b Lower contact terminal 2 Vacuum interrupter 2a Fixed contact 3 Moving contact 4 Contact force spring 5 Push Rod (Insulated coupling rod) 6 Opening spring 7 Rocker Arm (Transmission Lever)
  • Page 11: Interlocks

    ABB IB 6.2.15.7-1C MECHANISM AND OPERATION NTER OCKS The ADVAC™ breaker contains a number of interlocks. A description of each interlock follows as encountered during racking of the breaker into the breaker compartment. DANGER MODIFICATION TO INTERLOCKS CAN RESULT IN HAZARDOUS CONDITIONS TO PERSONNEL AND EQUIPMENT.
  • Page 12: Manual Operation

    ABB IB 6.2.15.7-1C MECHANISM AND OPERATION ANUAL PERATION (Refer to Table 2 & Appendix A) The breaker can be operated manually or electrically. The manual Charging Handle is required for manual operation. 1. Inspect initial state of the breaker to determine the operations available (Refer to Table 1 and Fig.2) a.
  • Page 13: Electrical Operation

    Test and Connect positions. Optional test jumpers and test cabinets to connect control power to a withdrawn circuit breaker are available (contact the local ABB sales office for details). 1. Inspect initial state of the breaker to determine the operations available a.
  • Page 14: Control Scheme

    ABB IB 6.2.15.7-1C MECHANISM AND OPERATION ONTROL CHEME ADVAC™ circuit breakers are available with two control packages. The standard package (see Appendix D) includes charge, close, and open functions, and 4a and 4b auxiliary contacts for customer use. The optional package (see Appendix D) adds to the standard package 5a and 4b auxiliary contacts for customer use as well as an optional second open coil and/or under voltage (UV) open/trip device if required.
  • Page 15 ABB IB 6.2.15.7-1C MECHANISM AND OPERATION Control voltage available to charging motor 33LSb Main Spring Charged 33LSb "open" Close Signal Start of Closing Operation Close operation complete Main spring discharged 33LSb "closed" Opening springs charged Compression Springs charged Main Spring Charged 33LSb "open"...
  • Page 16: Maintenance

    Charging Motor (D) in the mechanism (See Fig 4b). Remove any grease on the breaker frame. Use ISOFLEX TOPAS NB52 grease for lubrication (ABB No. ????????, 4 oz. tube). If the grease becomes caked and dirty, remove with a clean cloth and reapply lubrication. Use of incorrect lubricant may cause breaker to malfunction.
  • Page 17 ABB IB 6.2.15.7-1C MAINTENANCE See Fig 4B below DESCRIPTION DESCRIPTION ROCKER ARM AUXILIARY SWITCHES MOTOR LIMIT SWITCH MAIN SHAFT CLOSE COIL CHARGING MOTOR CLOSE PUSH BUTTON CLOSING SPRING OPEN PUSH BUTTON SECONDARY WIRING OPEN/CLOSE INDICATOR SHAFT SUPPORT BUSHING ANTI-PUMP CIRCUIT BOARD...
  • Page 18: Truck

    ABB IB 6.2.15.7-1C MAINTENANCE RUCK (Refer to Fig. 5) The truck requires visual inspection of hardware, lubrication and operations during routine maintenance. With the breaker outside the cell, verify all visible hardware tightness, including handles (1) and wheels (2). Wheels should rotate freely by hand movement. Replace or tighten any missing or loose hardware.
  • Page 19: Control Wiring

    Apply distilled water to the cloth to remove any difficult dirt. DO NOT return the breaker into service until the insulation surfaces are completely dry. Lubrication on the primary contacts should be inspected during routine maintenance. Use NO-OX-ID special grade-A grease for the lubrication of primary contacts (ABB No. 713222A, 1 Pt. can).
  • Page 20 ABB IB 6.2.15.7-1C MAINTENANCE A. Current energizes 52TC CAUTION Applying abnormally high voltage across a pair of open contacts in vacuum may produce X-radiation. The radiation may increase with the increase in voltage and/or decrease in contact spacing. It is recommended that all operating personnel stand at least one meter away and in front of the circuit breaker during testing.
  • Page 21: G&T Device

    ABB IB 6.2.15.7-1C G&T DEVICE SIMPLE G&T D EVICE The G&T device is designed for use in grounding and/or testing a circuit. The device is a manual cable device. The cables are used to provide a solid path to the main ground bus of the switchgear though the automatic ground of the G&T device.
  • Page 22 PRIMARY DISCONNECT (“FINGERS”); 1200/2000A, TO 50KA SHORT CIRCUIT 706741T11 PRIMARY DISCONNECT (“FINGERS”); 3000A, TO 50KA SHORT CIRCUIT NOTE: The parts listed above are available from ABB for field use or replacement. Consult your ABB sales representative for current pricing and availability.
  • Page 23: Dummy Breaker Device

    PRIMARY DISCONNECT (“FINGERS”); 1200/2000A, TO 50KA SHORT CIRCUIT 706741T11 PRIMARY DISCONNECT (“FINGERS”); 3000A, TO 50KA SHORT CIRCUIT NOTE: The parts listed above are available from ABB for field use or replacement. Consult your ABB sales representative for current pricing and availability.
  • Page 24: Optional Accessories

    ABB IB 6.2.15.7-1C OPTIONAL ACCESSORIES IFTING The lifting hook is designed for general lifting and lowering of the device, such as for removal from shipping pallets or for lifting onto and off of work tables. The lifting hook is not designed to be used for insertion or removal of the circuit breaker from the switchgear compartment, instead, use the appropriate optional lift truck.
  • Page 25: Appendices

    ABB IB 6.2.15.7-1C APPENDICES APPENDIX A BASIC BREAKER LAYOUT All ADVAC breakers have the same basic layout regardless of rating or pole configuration. Description FRONT PLATE ASSEMBLY CLOSE PUSH BUTTON OPEN PUSH BUTTON CLOSE/OPEN INDICATOR CHARGING PAWL CHARGED/DISCHARGED INDICATOR RACKING SCREW...
  • Page 26: Appendix B: Basic Breaker Dimensions And Weights

    ABB IB 6.2.15.7-1C APPENDICES APPENDIX B BASIC BREAKER DIMENSIONS AND WEIGHTS All ADVAC breakers of this style have the same basic dimensions (i.e. pole spacing) regardless of pole configuration. RAWOUT CATALOGUE DIGITS CATALOGUE DIGIT CATALOGUE DIGIT WEIGHT #1-3 (approx lbs.)
  • Page 27 ABB IB 6.2.15.7-1C APPENDICES APPENDIX B BASIC BREAKER DIMENSIONS AND WEIGHTS All ADVAC breakers of this style have the same basic dimensions (i.e. pole spacing, mounting locations) regardless of pole configuration. Hole patterns do change dependent upon the ampacity of the breaker.
  • Page 28 ABB IB 6.2.15.7-1C APPENDIX B ADVAC SSEMBLIES SED ON Assembled Pole Embedded Pole P3 Embedded Pole P2 15kV 2000A 50 kA 15kV / 1200A / 25 - 40kA 15kV 2000A 25 - 40kA 15kV 3000A 40 & 50kA ADVAC Pole Assemblies and spacing...
  • Page 29: Appendix Cclose/Open Coil Data

    ABB IB 6.2.15.7-1C APPENDICES APPENDIX C CLOSE/OPEN COIL DATA Following are the basic characteristics for the CLOSE and OPEN coils used on the ADVAC breakers. Resistance ranges may be used to identify the nominal voltage rating of a coil. All coils are DC voltage coils. AC power is rectified in the coil mounting assembly.
  • Page 30: Appendix Dwiring Diagrams

    ABB IB 6.2.15.7-1C APPENDICES APPENDIX D WIRING DIAGRAMS RAWOUT TANDARD IRING The schematic shows the basic wiring scheme for drawout breaker with standard wiring. This wiring includes four “a” and four “b” auxiliary contacts. If the optional pin monitoring circuit is used, only three “b”...
  • Page 31 ABB IB 6.2.15.7-1C APPENDICES APPENDIX D WIRING DIAGRAMS RAWOUT PTIONAL IRING The schematic shows the basic wiring scheme for drawout breaker with optional wiring. This wiring includes nine “a” and eight “b” auxiliary contacts. If the optional pin monitoring circuit is used, only seven “b”...
  • Page 32: Appendix E: Circuit Breaker Renewal Parts

    ABB IB 6.2.15.7-1C APPENDIX E CIRCUIT BREAKER RENEWAL PARTS AND ACCESSORIES: The parts listed below are available from ABB for field use or replacement. Consult your ABB sales representative for current pricing and availability. CCESSORIES Part # Qty/Breaker Description 14020P00...
  • Page 33 ABB IB 6.2.15.7-1C APPENDIX E CIRCUIT BREAKER RENEWAL PARTS AND ACCESSORIES: The parts listed below are available from ABB for field use or replacement. Consult your ABB sales representative for current pricing and availability. LECTRICAL ONTROL Part # Qty/Breaker Description 18081G00 STANDARD WIRING ASSEMBLY (“AA3”...
  • Page 34 ABB IB 6.2.15.7-1C ABB Inc. Circuit Breaker Technology Solutions 2300 Mechanicsville Highway Florence, SC 29501 Toll free 1-877-SOS-CBTS or +1 (843) 413-4700 Fax +1 (843) 413-4850 www.abb.com/mediumvoltage...

This manual is also suitable for:

Advac

Table of Contents