Functionality
Parameter
Digital inputs
Functionality of
digital inputs
(encoder, fast
counter, counter,
interrupt)
Digital outputs
2022/01/31
Value
PM5012-T-ETH
PM5012-R-ETH
6
6 DI fast input 24 V DC (max. 5
kHz)
usable as
●
6 DI 24 V DC standard
●
2 channel 5 kHz encoder with
frequency measurement or
●
2 channel 5 kHz encoder with
frequency measurement and
with touch/reset using standard
DI or
●
2 fast counter (5 kHz)
●
4 DI as interrupt input with
1 dedicated interrupt task and
input information
4
3ADR010278, 3, en_US
Device specifications
Processor modules > AC500-eCo
PM5032-T-ETH
PM5032-R-ETH
PM5052-T-ETH
PM5052-R-ETH
PM5072-
T-2ETH(W)
12
4 DI fast input 24 V DC (max. 200
kHz)
usable as
●
4 DI 24 V DC standard or
●
4 fast counter (100 kHz) or
●
2 A/B encoder (200 kHz) with
frequency measurement or
●
2 full A/B encoders 0 and 1 (200
kHz) with frequency measure-
ment and with touch/reset using
standard highspeed (5 kHz) DI
●
1 full A/B encoder 0 (200 kHz)
with frequency measurement
and optional with touch/reset
using 2 touch/sync inputs with
A/B encoder 0
4 DI fast input 24 V DC (5 kHz)
usable as
●
4 DI 24 V DC standard or
●
4 DI as interrupt input with
1 dedicated interrupt task and
input information
●
4 touch/sync inputs with A/B
encoder 0 or 1
4 standard DI 24 V DC
8
6
25