Siemens SINAMICS G120X Operating Instructions Manual page 1099

Infrastructure converter for hvac/water/wastewater
Hide thumbs Also See for SINAMICS G120X:
Table of Contents

Advertisement

690 V converters
Frame Size
FSD
FSE
FSF
FSG
FSH
FSJ
The rated output currents in bold refer to the default pulse frequency at 45 °C ambient temperature.
In the factory setting, the converter starts with a pulse frequency of 4 kHz and reduces automatically
1)
the pulse frequency to the associated required frequencies when loaded. When the load decreases,
the pulse frequency is increased automatically up to 4 kHz.
The values of the rated current refer to a pulse frequency of 2 kHz at 45 °C ambient temperature and
are reached at any time by the automatic adaptation of the output pulse frequency.
SINAMICS G120X converter
Operating Instructions, 06/2019, FW V1.01, A5E44751209B AC
Rated power based on
Output current (A) (at 45 °C ambient temperature) for a
LO (kW)
pulse frequency of
2 kHz
3
6
4
7
5.5
10
7.5
13
11
16
15
21
18.5
25
22
29
30
38
37
46
45
58
55
68
75
90
90
112
110
128
132
158
160
196
200
236
250
288
315
330
355
385
400
420
450
470
500
520
560
580
630
650
Technical data
11.5 Derating data
4 kHz
3.6
4.2
6
7.8
9.6
12.6
15
17.4
22.8
27.6
34.8
40.8
54
67.2
76.8
94.8
118
142
173
215
1)
250
1)
273
1)
306
1)
338
1)
377
1)
423
1)
1097