Extended Scope For Adaptation; Bico Technology: Basic Principles - Siemens SINAMICS G120 Operating Instructions Manual

Frequency converter
Hide thumbs Also See for SINAMICS G120:
Table of Contents

Advertisement

Introduction

1.5 Extended scope for adaptation

1.5
Extended scope for adaptation
1.5.1

BICO technology: basic principles

Principle of operation of BICO technology
Open/closed-loop control functions, communication functions as well as diagnostic and
operator functions are implemented in the inverter. Every function comprises one or several
BICO blocks that are interconnected with one another.
Inputs
MOP enable (higher)
p1035
MOP enable (lower)
p1036
Figure 1-1
Most of the BICO blocks can be parameterized. You can adapt the blocks to your application
using parameters.
You cannot change the signal interconnection within the block. However, the interconnection
between blocks can be changed by interconnecting the inputs of a block with the appropriate
outputs of another block.
The signal interconnection of the blocks is realized, contrary to electric circuitry, not using
cables, but in the software.
Figure 1-2
Binectors and connectors
Connectors and binectors are used to exchange signals between the individual BICO blocks:
● Connectors are used to interconnect "analog" signals. (e.g. MOP output speed)
● Binectors are used to interconnect "digital" signals. (e.g. 'Enable MOP up' command)
16
Parameter
MOP output
MOP
Example of a BICO block: Motorized potentiometer (MOP)
p0840
DI 0
r0722.0
Index [0]
Example: Signal interconnection of two BICO blocks for digital input 0
Output
speed
[rpm]
r1050
ON/
OFF1
Inverter with CU240B-2 and CU240E-2 Control Units
Operating Instructions, 01/2011, FW 4.4, A5E02299792B AB

Advertisement

Table of Contents
loading

Table of Contents