Chapter 12 Description of Parameter SettingsC2000 Series
PM Sensorless Control Word
Settings
Bit No.
0
Reserved
1
Reserved
2
Choose a control mode to
statrt.
3
Choose a mode to stop .
4
Reserved
5
Choose a control mode to stop 0 : When lower than Pr10-40, coast to stop
6
Reserved
7
Reserved
Frequency Point when switch from I/F mode to PM Sensorless mode
Settings
Frequency Point when switch from PM Sensorless Observation mde to I/F mode
Settings
I/F mode, low pass-filter time
Settings
Initial Angle Detection Time
Settings
PM Sensorless Adjustment Procedure
1. When using high frequency standstill VFD parameter tuning, use VFD software to monitor
adjustment procedure. To download VFD Sotware go to:
http://www.delta.com.tw/product/em/download/download_main.asp?act=3&pid=1&cid=1&tpid=3
2. Testing PM High Frequency Standstill VFD (calculation of Rs, Ld, Lg)
Procedures:
A.
Set control mode as VF mode (Pr00-10=0, Pr00-11=0
B.
Output Frequency of Motor 1
C.
Output Voltage of Motor 1
D.
Induction Motor and Permanent Magnet Motor Selection (Pr05-33=1)
E.
Full-load current of Permanent Magnet Motor(Pr05-34
F.
Set Moto Auto Tuning Pr 05-00 =13;
run the drive.
3. Set control mode as PM sensorless Mode (Parameters 00-10=0, 00-11=6)
4. Set VFD Prameters
0000~FFFFh
Function
0 :Start by IF mode
1: Start by VF mode
0 :Stop by IF mode
1 :Stop by VF mode
If lower than Pr10-40, decelerate to stop by VF mode.
0.00~600.00Hz
0.00~600.00Hz
0.0~6.0 sec
0~20 ms
(Pr01-01)
(Pr01-02)
Description
High frequency and blocked rotor test for PM motor. Then
170
Factory Setting: 0000
Factory Setting: 20.00
Factory Setting: 20.00
Factory Setting: 0.2
Factory Setting: 5