Aci Low/Mid/High Point; Aci Proportional Low/Mid/High Point; Positive Aui Voltage Low Point; Positive Aui Voltage Proportional Low Point - Delta C2000 series User Manual

Classical field oriented control ac motor drive
Hide thumbs Also See for C2000 series:
Table of Contents

Advertisement

ACI Low Point
Settings
ACI Proportional Low Point
Settings
ACI Mid Point
Settings
ACI Proportional Mid Point
Settings
ACI High Point
Settings
ACI Proportional High Point
Settings
 When Pr.03-29=1, ACI setting is 0-10V and the unit is in voltage (V).
 When Pr.03-29≠1, ACI setting is 0-20mA or 4-20mA and the unit is in current (mA).
 When setting analog input ACI to frequency command, it 100% corresponds to Fmax (Pr.01-00
Max. operation frequency).
 The 3 parameters (Pr03-57, Pr03-59 and Pr03-61) must meet the following argument: P03-57 <
P03-59 < P03-61. The 3 proportional points (Pr03-58, Pr03-60 and Pr03-62) doesn't have any limit.
Between two points is a linear calculation.
 The output % will become 0% when the ACI input value is lower than low point setting.
For example:
P03-57 = 2mA; P03-58 = 10%. The output will become 0% when AVI input is lower than 2mA. If
the ACI input is swing between 2mA and 2.1mA, drive's output frequency will beats between 0%
and 10%.

Positive AUI Voltage Low Point

Settings

Positive AUI Voltage Proportional Low Point

Settings
Chapter 12 Description of Parameter SettingsC2000 Series
Pr.03-29=1, 0.00~10.00V
Pr.03-29≠1, 0.00~20.00mA
0.00~100.00%
03-29=1, 0.00~10.00V
03-29≠1, 0.00~20.00mA
0.00~100.00%
03-29=1, 0.00~10.00V
03-29≠1, 0.00~20.00mA
0.00~100.00%
0.00~10.00V
0.00~100.00%
12-
83
Factory Setting: 4.00
Factory Setting: 0.00
Factory Setting: 12.00
Factory Setting: 50.00
Factory Setting: 20.00
Factory Setting: 100.00
Factory Setting: 0.00
Factory Setting: 0.00