When 3-phase current output unbalance value has exceeds Pr06-60 setting, drive will trip up GFF
and stop output immediately.
Disable Level of dEb
Settings
Fault Record 1 (day)
Fault Record 2 (day)
Fault Record 3 (day)
Fault Record 4 (day)
Settings
Fault Record 1 (min)
Fault Record 2 (min)
Fault Record 3 (min)
Fault Record 4 (min)
Settings
Pr.06-63 to Pr.06-68 are used to record the operation time for 6 malfunctions and it can also check
if there is any wrong with the drive according to the internal time.
When the malfunction occurs during operation, it records fault in Pr.06-17~06-22 and operation
time is recorded in Pr.06-63~06-68.
For example: When the first fault ovA occurs after operation 3000 min., second fault ovd occurs at
3482 min., third fault ovA occurs at 4051 min., fourth fault ocA at 5003 min., fifth fault ocA at 5824
min., sixth fault ocd occurs at 6402 min. and seven fault ocS at 6951 min..
It'll be recorded as the following table:
It will be recorded as the following table:
First fault
Second fault
Third fault
Chapter 12 Description of Parameter SettingsC2000 Series
230V series: 0.0~220.0 Vic
460V series: 0.0~440.0 Vic
0~65535 days
0~1439 min
Pr.06-17
ovA
Pr.06-17
ovd
Pr.06-18
ovA
Pr.06-17
ovA
12-
Factory Setting: 180.0/360.0
Pr.06-63
3000 ovA occurs at the 3000 min
Pr.06-63
3482
Pr.06-64
3000
Pr.06-63
4051
120
Factory Setting: Read only
Factory Setting: Read only
after operating.
3482-3000=482 min
ovd occurs at 482 min after
last fault (ovA)
4051-3482=569 min
ovA occurs at 569 min after
last fault (ovd)