Chapter 12 Description of Parameter SettingsC2000 Series

4. Address list

Content

AC drive parameters

Command write only

Status monitor read
only
Address
GGnnH GG means parameter group, nn means parameter number, for
example, the address of Pr 4-01 is 0401H.
2000H
00B:No function
Bit1~0
01B:Stop
10B:Run
11B:JOG+RUN
Bit3~2
Reserved
00B:No function
Bit5~4
01B:FWD
10B:REV
11B:Change direction
00B:1st accel/decel.
Bit7~6
01B:2nd accel/decel
10B:3rd accel/decel
11B:4th accel/decel
Bit11~8 000B: master speed
0001B: 1st
0010B: 2nd
0011B: 3rd
0100B: 4th
0101B: 5th
0110B: 6th
0111B: 7th
1000B: 8th
1001B: 9th
1010B: 10th
1011B: 11th
1100B: 12th
1101B: 13th
1110B: 14th
1111B: 15th
Bit12
1: Enable bit06-11 function
Bit14~13 00B:No function
01B:Operated by digital keypad
10B:Operated by Pr.00-21 setting
11B:Change operation source
Bit15
Reserved
2001H Frequency command
1:EF (external fault) on
2002H
Bit0
1:Reset
Bit1
1:B.B ON
Bit2
Bit15~3 Reserved
2100H Error code: refer to Pr.06-17 to Pr.06-22
2101H
Bit1~0
AC Drive Operation Status
00B: Drive stops
01B: Drive decelerating
10B: Drive standby
11B: Drive operating
Bit2
1:JOG Command
152
Function
Step Speed Frequency
Step Speed Frequency
Step Speed Frequency
Step Speed Frequency
Step Speed Frequency
Step Speed Frequency
Step Speed Frequency
Step Speed Frequency
Step Speed Frequency
Step Speed Frequency
Step Speed Frequency
Step Speed Frequency
Step Speed Frequency
Step Speed Frequency
Step Speed Frequency