Plc Command Mask; Source Of The Master Frequency Command(Auto) - Delta C2000 series User Manual

Classical field oriented control ac motor drive
Hide thumbs Also See for C2000 series:
Table of Contents

Advertisement

Heavy Duty Factory
Setting
Models
Setting Range
Normal Duty Factory
Setting
Heavy Duty Factory
Setting
Carrier
Frequency
1kH z
8kH z
15kHz
 From the table, we see that the PWM carrier frequency has a significant influence on the
electromagnetic noise, AC motor drive heat dissipation, and motor acoustic noise. Therefore, if the
surrounding noise is greater than the motor noise, lower the carrier frequency is good to reduce the
temperature rise. Although it is quiet operation in the higher carrier frequency, the entire wiring and
interference resistance should be considerate.
 When the carrier frequency is higher than the factory setting, it needs to protect by decreasing the
carrier frequency. See Pr.06-55 for the related setting and details.
Reserved

PLC Command Mask

Settings
 This parameter determines if frequency command or control command is occupied by PLC
Source of the Master Frequency Command(AUTO)
Settings
1-20HP [0.75-15kW]
02~15kHz
8kHz
Acoustic
Noise
Significant
Minimal
Bit 0: Control command by PLC force control
Bit 1: Frequency command by PLC force control
Bit 2: Position command by PLC force control
Bit 3: Torque command by PLC force control
0: Digital keypad
1: RS-485 serial communication
2: External analog input (Pr.03-00)
3: External UP/DOWN terminal
Chapter 12 Description of Parameter SettingsC2000 Series
2kHz
460V Series
25-75HP [18.5-55kW] 100-475HP [75-355kW]
02~10kHz
6kHz
2kHz
Electromagnetic
Noise or Leakage
Current
Minimal
Significant
Significant
12-13
02~09kHz
4kHz
Heat
Current
Dissipation
Wave
Minimal
Factory Setting: Read Only
Factory Setting: 0