Delta C2000 series User Manual page 406

Classical field oriented control ac motor drive
Hide thumbs Also See for C2000 series:
Table of Contents

Advertisement

Chapter 14 Fault Codes and Descriptions C2000 Series
ID*
Fault Name
Fault
6
ocS
Oc at stop
Fault
7
ovA
Ov at accel
Fault
8
ovd
Ov at decel
Fault
9
ovn
Ov at normal SPD
Fault
10
ovS
Ov at stop
Fault
11
LvA
Lv at accel
Fault
12
Lvd
Lv at decel
Fault
13
Lvn
Lv at normal SPD
Fault
14
LvS
Lv at stop
Fault Descriptions
Hardware failure in
current detection
DC BUS over-voltage
during acceleration
(230V: DC 450V; 460V:
DC 900V)
DC BUS over-voltage
during deceleration
(230V: DC 450V; 460V:
DC 900V)
DC BUS over-voltage at
constant speed (230V: DC
450V; 460V: DC 900V)
Hardware failure in
voltage detection
DC BUS voltage is less
than Pr.06-00 during
acceleration
DC BUS voltage is less
than Pr.06-00 during
deceleration
DC BUS voltage is less
than Pr.06-00 in constant
speed
DC BUS voltage is less
than Pr.06-00 at stop
Corrective Actions
Return to the factory
1. Check if the input voltage falls within the rated AC
motor drive input voltage range.
2. Check for possible voltage transients.
3. If DC BUS over-voltage due to regenerative
voltage, please increase the acceleration time or
add an optional brake resistor.
1. Check if the input voltage falls within the rated AC
motor drive input voltage range.
2. Check for possible voltage transients.
3. If DC BUS over-voltage due to regenerative
voltage, please increase the Deceleration Time or
add an optional brake resistor.
1. Check if the input voltage falls within the rated AC
motor drive input voltage range.
2. Check for possible voltage transients.
3. If DC BUS over-voltage due to regenerative
voltage, please increase the Deceleration Time or
add an optional brake resistor.
1. Check if the input voltage falls within the rated AC
motor drive input voltage range.
2. Check for possible voltage transients.
1.
Check if the input voltage is normal
2.
Check for possible sudden load
1.
Check if the input voltage is normal
2.
Check for possible sudden load
1.
Check if the input voltage is normal
2.
Check for possible sudden load
1.
Check if the input voltage is normal
2.
Check for possible sudden load
14-2