Mid-point Frequency 2 of Motor 1
Settings
Mid-point Voltage 2 of Motor 1
Settings
Mid-point Frequency 2 of Motor 2
Settings
Mid-point Voltage 2 of Motor 2
Settings
Min. Output Frequency of Motor 1
Settings
Min. Output Voltage of Motor 1
Settings
Min. Output Frequency of Motor 2
Settings
Min. Output Voltage of Motor 2
Settings
 V/f curve setting is usually set by the motor's allowable loading characteristics. Pay special attention
to the motor's heat dissipation, dynamic balance, and bearing lubricity, if the loading characteristics
exceed the loading limit of the motor.
 There is no limit for the voltage setting, but a high voltage at low frequency may cause motor
damage, overheat, and stall prevention or over-current protection. Therefore, please use the low
voltage at the low frequency to prevent motor damage.
 Pr.01-35 to Pr.01-42 is the V/f curve for the motor 2. When multi-function input terminals
230V series: 0.0~240.0V
460V series: 0.0~480.0V
0.00~600.00Hz
230V series: 0.0~240.0V
460V series: 0.0~480.0V
0.00~600.00Hz
230V series: 0.0~240.0V
460V series: 0.0~480.0V
0.00~600.00Hz
230V series: 0.0~240.0V
460V series: 0.0~480.0V
0.00~600.00Hz
230V series: 0.0~240.0V
460V series: 0.0~480.0V
Chapter 12 Description of Parameter SettingsC2000 Series
12-23
Factory Setting: 11.0/22.0
Factory Setting: 0.50
Factory Setting: 2.0/4.0
Factory Setting: 0.50
Factory Setting: 2.0/4.0
Factory Setting: 0.00
Factory Setting: 0.0/0.0
Factory Setting: 0.00
Factory Setting: 0.0/0.0