Rated Power Of Induction Motor 2 (Kw); Rated Speed Of Induction Motor 2 (Rpm); Pole Number Of Induction Motor 2; No-Load Current Of Induction Motor 2 (A) - Delta C2000 series User Manual

Classical field oriented control ac motor drive
Hide thumbs Also See for C2000 series:
Table of Contents

Advertisement

Settings
 This value should be set according to the rated frequency of the motor as indicated on the motor
nameplate. The factory setting is 90% X rated current.
Example: The rated current for 7.5HP (5.5kW) is 25A and factory setting is 22.5A. The range for
setting will be 10~30A.(25*40%=10A and 25*120%=30A)

Rated Power of Induction Motor 2 (kW)

Settings
 It is used to set rated power of the motor 2. The factory setting is the power of the drive.

Rated Speed of Induction Motor 2 (rpm)

Settings
 It is used to set the rated speed of the motor and need to set according to the value indicated on
the motor nameplate.

Pole Number of Induction Motor 2

Settings
 It is used to set the number of motor poles (must be an even number).

No-load Current of Induction Motor 2 (A)

Settings
 The factory setting is 40% X rated current.
Stator Resistance (Rs) of Induction Motor 2
Rotor Resistance (Rr) of Induction Motor 2
Settings
Magnetizing Inductance (Lm) of Induction Motor 2
Stator Inductance (Lx) of Induction Motor 2
Settings
Induction Motor 1/ 2 Selection
Settings
 It is used to set the motor that driven by the AC motor drive.
Chapter 12 Description of Parameter SettingsC2000 Series
10~120%
0~655.35 kW
0~65535
2~20
0 to the factory setting in Pr.05-13
0~65.535Ω
0~6553.5 mH
1: Motor 1
2: Motor 2
12-
94
Factory Setting: #.##
Factory Setting: 1710
Factory Setting: 4
Unit: Amper
Factory Setting: #.##
Factory Setting: #.###
Factory Setting: #.#
Factory Setting: 1