Chapter 2 InstallationC2000 Series
Model No.
External Internal
VFD022C43A/E
14
VFD037C43A/E
10
VFD040C43A/E
10
VFD055C43A/E
10
VFD075C43A/E
40
VFD110C43A/E
66
VFD150C43A/E
58
VFD185C43A/E
99
VFD220C43A/E
99
VFD300C43A/E
126
VFD370C43A/E
179
VFD450C43A/E
179
VFD550C43A/E
179
VFD750C43A/E
186
VFD900C43A/E
257
VFD1100C43A/E
223
VFD1320C43A/E
224
VFD1600C43A/E
289
VFD1850C43A/E
VFD2200C43A/E
VFD2800C43A/E
VFD3150C43A/E
VFD3550C43A/E
VFD4500C43A/E
The required airflow shown in chart is for installing single drive in a
confined space.
When installing the multiple drives, the required air volume should
be the required air volume for single drive X the number of the
drives.
Air flow rate for cooling
Flow Rate (cfm)
Total
External Internal
-
14
-
10
-
10
-
10
14
54
14
80
14
73
21
120
21
120
21
147
30
209
30
209
30
209
30
216
73
330
73
296
112
336
112
401
454
454
769
769
769
769
3
Flow Rate (m
/hr)
Total
24
-
24
17
-
17
17
-
17
17
-
17
68
24
92
112
24
136
99
24
124
168
36
204
168
36
204
214
36
250
304
51
355
304
51
355
304
51
355
316
51
367
437
124
561
379
124
503
381
190
571
491
190
681
771
771
1307
1307
1307
1307
2-4
Power dissipation of AC motor
drive
Power Dissipation
Loss External
Internal
(Heat sink)
71
33
103
38
116
42
134
46
216
76
287
93
396
122
369
138
476
158
655
211
809
184
929
218
1156
257
1408
334
1693
399
2107
491
2502
579
3096
687
The heat dissipation shown in
the chart is for installing single
drive in a confined space.
When installing the multiple
drives, volume of heat
dissipation should be the heat
dissipated for single drive X
the number of the drives.
Heat dissipation for each
model is calculated by rated
voltage, current and default
carrier.
Total
104
141
158
180
292
380
518
507
635
866
993
1147
1413
1742
2092
2599
3081
3783
4589
5772
6381
7156
8007
11894

Advertisement

Table of Contents
loading

Table of Contents