Digital Input Operation Setting; Multi-Function Output 1,2 (Relay 1,2); Multi-Function Output 3,4 (Mo1, Mo2); Output Terminal Of I/O Extension Card (Mo10-Mo20) Or (Ra10-Ra15) - Delta C2000 series User Manual

Classical field oriented control ac motor drive
Hide thumbs Also See for C2000 series:
Table of Contents

Advertisement

to prevent some uncertain interference that would cause error in the input of the digital terminals.
Under this condition, confirmation for this parameter would improve effectively, but the response
time will be somewhat delayed.
 When using MI8 as encoder pulse feedback input, this parameter will not be refered

Digital Input Operation Setting

Settings 0000h~FFFFh(0:N.O ; 1:N.C)
 The setting of this parameter is in hexadecimal.
 This parameter is to set the status of multi-function input signal (0: Normal Open;1: Normal Close)
and it is not affected by the SINK/SOURCE status..
 Bit0 is for FWD terminal, bit1 is for REV terminal and bit2 to bit15 is for MI1 to MI14.
 User can change terminal status by communicating.
For example, MI1 is set to 1 (multi-step speed command 1), MI2 is set to 2 (multi-step speed
command 2). Then the forward + 2
needs to be set by communication to run forward with 2nd step speed. No need to wire any
multi-function terminal.
Bit15 bit14 bit13 bit12 bit11 bit10 bit9 bit8 bit7 bit6 bit5 bit4 bit3 bit2 bit1 bit0
MI14 MI13 MI12 MI11 MI10 MI9 MI8 MI7 MI6 MI5 MI4 MI3 MI2 MI1
Multi-function Output 1 (Relay1)
Multi-function Output 2 (Relay2)
Multi-function Output 3 (MO1)
Multi-function Output 4 (MO2)
Output terminal of I/O extension card (MO10) or (RA10)
Output terminal of I/O extension card (MO11) or (RA11)
Output terminal of I/O extension card (MO12) or (RA12)
Output terminal of I/O extension card (MO13) or (RA13)
Output terminal of I/O extension card (MO14) or (RA14)
Output terminal of I/O extension card (MO15) or (RA15)
Output terminal of I/O extension card (MO16)
Output terminal of I/O extension card (MO17)
Output terminal of I/O extension card (MO18)
Output terminal of I/O extension card (MO19)
Output terminal of the I/O extension card (MO20)
Settings
0: No function
1: Operation Indication
Chapter 12 Description of Parameter SettingsC2000 Series
nd
step speed command=1001(binary)=9 (Decimal). Pr.02-12=9
12-43
Factory Setting: 0000
Factory Setting: 11
Factory Setting: 1
Factory Setting: 0