proportion to produce the same magnetic torque. That is the slip will be larger with the reduction
of synchronous frequency. The motor may stop when the synchronous frequency is decreased to
a specific value. Therefore, the slip serious affects the accuracy of motor speed at low speed.
 In another situation, when the drive uses with induction motor, the slip will be increased by the
increasing load. It also affects the accuracy of motor speed.
 This parameter can be used to set compensation frequency and reduce the slip to close the
synchronous speed when the motor runs in the rated current to raise the drive accuracy. When
the drive output current is larger than Pr.05-05 No-load Current of Induction Motor 1 (A), the drive
will compensation the frequency by this parameter.
 When the control method (Pr.00-11) is changed from V/f mode to vector mode, this parameter will
auto be set to 1.00. Otherwise, it will be set to 0.00. Please do the compensation of slip after
overload and acceleration. The compensation value should be increased from small to large
gradually. That is to add the output frequency with motor rated slip X Pr.07-27 Slip Compensation
Gain when the motor is rated load. If the actual speed ratio is slow than expectation, please
increase the setting. Otherwise, decrease the setting.
Reserved

Slip Deviation Level

Settings

Detection Time of Slip Deviation

Settings

Over Slip Treatment

Settings
 The Pr.07-29 to Pr.07-31 are to set allowable slip level/time and over slip treatment when the drive
is running.

Motor Hunting Gain

Settings
 The motor will have current wave motion in some specific area. It can improve this situation by
setting this parameter. (When it is high frequency or run with PG, it can be set to 0. when the
current wave motion happens in the low frequency, please increase Pr.07-32.)
0~100.0%
0: No detection
0.0~10.0 sec
0: Warn and keep operation
1: Warn and ramp to stop
2: Warn and coast to stop
3: No warning
0~10000
0: Disable
Chapter 12 Description of Parameter SettingsC2000 Series
133
Factory Setting: 0
Factory Setting:1.0
Factory Setting:0
Factory Setting:1000