 Bit 0~3: Control F page, unit of user defined value (Pr00-04 =d10, PID feedback) and the decimal
point of Pr00-26 which supports up to 3 decimal points.
 Bit 4~15: Control F page, unit of user defined value (Pr00-04=d10, PID feedback) and the display
units of Pr00-26 which supports up to 4 units

Max. User Defined Value

Settings
 When Pr.00-26 is NOT set to 0. The user defined value is enabled. The value of this parameter
should correspond to the frequency setting at Pr.01-00.
Example:
When the frequency at Pr. 01-00=60.00Hz, the max. user defined value at Pr. 00-26 is 100.0%.
That also means Pr.00-25 is set at 0021h to select % as the unit.
NOTE
The drive will display as Pr.00-25 setting when Pr.00-25 is properly set and Pr.00-26 is not 0.

User Defined Value

Settings
 Pr.00-27 will show user defined value when Pr.00-26 is not set to 0.
 User defined function is valid when:
1. Pr.00-20 is set to digital keypad control
2. RS-285 communication input control.
3. PID function enable
Bit 4~15: user defined unit
000xh: Hz
001xh: rpm
002xh: %
003xh: kg
0
0 0
0
h
0: Disable
0~65535 (when Pr.00-25 set to no decimal place)
0.0~6553.5 (when Pr.00-25 set to 1 decimal place)
0.0~655.35 (when Pr.00-25 set to 2 decimal place)
0.0~65.535 (when Pr.00-25 set to 3 decimal place)
Read only
Chapter 12 Description of Parameter SettingsC2000 Series
u se r d e fin e d d e cima l p la ce
0:no decimal place
1:one
decimal place
2:tw
o decimal place
3:three
decimal place
u se r d e fin e d u n it
0: Hz
1: rpm
2: %
3: kg
12-16
Factory Setting: 0
Factory Setting: Read only