Settings
Functions
57~70 Reserved

UP/DOWN Key Mode

Settings

Constant speed. The Accel. /Decel. Speed of the UP/DOWN Key

Settings
 These settings are used when multi-function input terminals are set to 19/20. Refer to Pr.02-09 and
02-10 for the frequency up/down command.
 Pr.02-09 set to 0: it will increase/decrease frequency command (F) by the external terminal
UP/DOWN key as shown in the following diagram. In this mode, it also can be controlled by
UP/DOWN key on the digital keypad.
F requenc y
External ter minal
UP k ey
 Pr.02-09 set to 1: it will increase/decrease frequency command (F) by the setting of
acceleration/deceleration (Pr.01-12~01-19) and only be valid during operation.
Mu lti -fu ncti on
i np ut te rmi na l
1 0 Fr eq ue ncy
i ncr ea sed comma nd

Digital Input Response Time

Settings
 This parameter is used to set the response time of digital input terminals FWD, REV and MI1~MI8.
 It is used for digital input terminal signal delay and confirmation. The delay time is confirmation time
0: Up/down by the accel/decel time
1: Up/down constant speed (Pr.02-10)
0.01~1.00Hz/ms
F requenc y c ommand
ON
Fr eq ue ncy
0.000~30.000 sec
Chapter 12 Description of Parameter SettingsC2000 Series
Descriptions
Bit 0
REM
0
LOC
1
T ime
UP
DOWN
OFF
Fr eq ue ncy
co mman d
In cre ase d b y acce le ra tio n ti me
ON
12-42
Factory Setting: 0
Factory Setting: 0.01
Ml1~15
Ml1~15
DCM
VFD-C
Ti me
OFF
Factory Setting: 0.005