Positive AUI Voltage Mid Point
Settings
Positive AUI Voltage Proportional Mid Point
Settings
Positive AUI Voltage High Point
Settings
Positive AUI Voltage Proportional High Point
Settings
 When setting positive voltage AUI to frequency command, it 100% corresponds to Fmax (Pr.01-00
Max. operation frequency) and the motor runs in forward direction.
 Three of the positive voltage AUI points can be set according to user's demand on voltage and
proportion, there is no setting limit for AUI points.
Negative AUI Voltage Low Point
Settings
Negative AUI Voltage Proportional Low Point
Settings
Negative AUI Voltage Mid Point
Settings
Negative AUI Voltage Proportional Mid Point
Settings
Negative AUI Voltage High Point
Settings
Negative AUI Voltage Proportional High Point
Settings
 When setting negative voltage AUI to frequency command, it 100% corresponds to Fmax (Pr.01-00
Max. operation frequency) and the motor runs in reverse direction.
 Three of the negative voltage AUI points can be set according to user's demand on voltage and
proportion, there is no setting limit for AUI points.
Chapter 12 Description of Parameter SettingsC2000 Series
0.00~10.00V
0.00~100.00%
0.00~10.00V
0.00~100.00%
0.00~-10.00V
0.00~-100.00%
0.00~-10.00V
0.00~-100.00%
0.00~-10.00V
0.00~-100.00%
12-
84
Factory Setting: 5.00
Factory Setting: 50.00
Factory Setting: 10.00
Factory Setting: 100.00
Factory Setting: 0.00
Factory Setting: 0.00
Factory Setting: -5.00
Factory Setting: -50.00
Factory Setting: -10.00
Factory Setting: -100.00