Exception Response; Example, The Address Of Pr 4-01 Is 0401H - Delta C2000 series User Manual

Classical field oriented control ac motor drive
Hide thumbs Also See for C2000 series:
Table of Contents

Advertisement

Chapter 12 Description of Parameter SettingsC2000 Series
Content
Content
AC drive Parameters GGnnH GG means parameter group, nn means parameter number, for

5. Exception response:

The AC motor drive is expected to return a normal response after receiving command messages
from the master device. The following depicts the conditions when no normal response is replied to
the master device.
The AC motor drive does not receive the messages due to a communication error; thus, the AC
motor drive has no response. The master device will eventually process a timeout condition.
The AC motor drive receives the messages without a communication error, but cannot handle them.
An exception response will be returned to the master device and an error message "CExx" will be
displayed on the keypad of AC motor drive. The xx of "CExx" is a decimal code equal to the
exception code that is described below.
Address
2211H The status of digital output (ON/OFF), refer to Pr.02-18 (as Pr.
00-04 NOTE 4)
2212H The multi-step speed that is executing (S)
2213H The corresponding CPU pin status of digital input (d.) (as Pr.
00-04 NOTE 3)
2214H The corresponding CPU pin status of digital output (O.) (as Pr.
00-04 NOTE 4)
2215H Number of actual motor revolution (PG1 of PG card) (P.) it will
start from 9 when the actual operation direction is changed or
keypad display at stop is 0. Max. is 65535
2216H Pulse input frequency (PG2 of PG card)(S.)
2217H Pulse input position (PG card PG2), maximum setting is
65535.
2218H Position command tracing error
2219H Display times of counter overload (0.00~100.00%)
221AH GFF in % (G.)
221BH DCbus voltage ripples (Unit: Vdc) (r.)
221CH PLC register D1043 data (C)
221DH Pole of Permanent Magnet Motor
221EH User page displays the value in physical measure
221FH Output Value of Pr.00-05
2220H
Number of motor tunrns when drive operates (keeping when
drive stops, and reset to zero when operation)
2221H Opeartion position of motor (keeping when drive stops, and
reset to zero when operation)
2222H Fan speed of the drive (%)
2223H Control mode of the drive 0: speed mode 1: torque mode
2224H Carrier frequency of the drive
Address Function

example, the address of Pr 4-01 is 0401H.

2225H Carrier frequency of the drive
2226H Drive status
2227H Drive's estimated output torque(positive or negative direction)
2228H Torque command
2229H KWH display
222AH PG2 pulse input in Low Word
222BH PG2 pulse input in High Word
222CH Motor actual position in Low Word
222DH Motor actual position in High Word
222EH PID reference
222FH PID offset
2230H PID output frequency
154
Function

Advertisement

Table of Contents
loading