Chapter 5 Main Circuit TerminalsC2000 Series
Power
Power
Adaptor
R
S
T
Terminals
R/L1, S/L2, T/L3
U/T1, V/T2, W/T3
+1, +2
+1/DC+, -/DC-
B1, B2
R/L11
S/L12
T/L13
R/L21
S/L22
T/L23
AC line input terminals 3-phase
AC drive output terminals for connecting 3-phase induction motor
Applicable to frame A~C
Connections for DC reactor to improve the power factor. It needs to remove the
jumper for installation.
Connections for brake unit (VFDB series)
(for 230V models:
22kW, built
(for 460V models:
30kW, built
Common DC Bus
Connections for brake resistor (optional)
Earth connection, please comply with local regulations.

Main power terminals

Do not connect 3-phase model to one-phase power. R/L1, S/L2 and T/L3
has no phase-sequence requirement, it can be used upon random
selection.
It is recommend to add a magnetic contactor (MC) to the power input wiring
to cut off power quickly and reduce malfunction when activating the
protection function of the AC motor drive. Both ends of the MC should have
an R-C surge absorber.
Fasten the screws in the main circuit terminal to prevent sparks condition
made by the loose screws due to vibration.
Please use voltage and current within the specification.
When using a general GFCI (Ground Fault Circuit Interrupter), select a
current sensor with sensitivity of 200mA or above and not less than
0.1-second operation time to avoid nuisance tripping.