PDFF Gain Value
Settings
After finishing estimating and set Pr.11-00 to bit 0=1 (auto tuning), using Pr.11-13 to reduce
overshoot. Please adjust PDFF gain value by actual situation.
This parameter will be invalid when Pr.05-24 is set to 1.
Low-pass Filter Time of ASR Output
Settings
It is used to set the filter time of ASR command.
Notch Filter Depth
Settings
Notch Filter Frequency
Settings
This parameter is used to set resonance frequency of mechanical system. It can be used to
suppress the resonance of mechanical system.
The larger number you set Pr.11-15, the better suppression resonance function you will get.
The notch filter frequency is the resonance of mechanical frequency.
Forward Motor Torque Limit
Forward Regenerative Torque Limit
Reverse Motor Torque Limit
Reverse Regenerative Torque Limit
Settings
The motor drive rated current is 100%. The settings for Pr.11-17 to Pr.11-20 will compare with
Pr.03-00=7, 8, 9, 10. The minimum of the comparison result will be torque limit. Please refer the
chart as below.
Calculation equation for motor rated torque:
0~200%
frequency
PI
0.000~0.350 sec
0~20db
0.00~200.00Hz
0~500%
Chapter 12 Description of Parameter SettingsC2000 Series
PDFF
175
Factory Setting: 30
T ime
Factory Setting: 0.008
Factory Setting: 0
Factory Setting: 0.00
Factory Setting: 500