Thermal Relay - Delta C2000 series User Manual

Classical field oriented control ac motor drive
Hide thumbs Also See for C2000 series:
Table of Contents

Advertisement

NFB
R/L1
S/L2
T/L3
O.L.
MC
S A
Varistor

Thermal relay

or Temperature Switch
Trip Contact
When AC Drive is equipped with a DC reactor, please read user manual to know th
wiring method of input circuit of brake unit +(P).
Do Not connect input circuit -(N) to the neutral point of the power system.
2.
If damage to the drive or other equipment is due to the fact that the brake resistors and brake modules in use are not
provided by Delta, the warranty will be void.
3.
Take into consideration the safety of the environment when installing the brake resistors. If the minimum resistance value is
to be utilized, consult local dealers for the calculation of Watt figures.
4.
When using more than 2 brake units, equivalent resistor value of parallel brake unit can't be less than the value in the
column "Minimum Equivalent Resistor Value for Each AC Drive" (the right-most column in the table). Please read the wiring
information in the user manual of brake unit thoroughly prior to operation
5.
This chart is for normal usage; if the AC motor drive is applied for frequent braking, it is suggested to enlarge 2~3 times of
the Watts.
6.
Thermal Relay:
Thermal relay selection is basing on its overload capability. A standard braking capacity for C2000 is 10%ED (Tripping
time=10s). The figure below is an example of 406V, 110kw AC motor drive. It requires the thermal relay to take 260%
overload capacity in 10s (Host starting) and the braking current is 126A. In this case, user should select a rated 50A thermal
relay. The property of each thermal relay may vary among different manufacturer, please carefully read specification.
V FD
MC
R/L1
U/T1
S/L2
V/T2
T/L3
W/T3
+(P)
- (N)
+
(P)
Brake unit
VFDB
XXXX
MASTER
60
40
30
20
10
8
6
4
3
2
1
0.8
0.6
0.4
0.3
0.8
1
1.5
Multiple of current setting
Chapter 7 Optional AccessoriesC2000 Series
MOTOR
IM
T hermal relay
-
B1
(N)
Brake
O.L.
Resistor
B2
MASTER
M1 M2
Temperature
switch
5
2
4
6
3
7-3
T hermal relay
-
+
B1
(P)
(N)
Brake
O.L.
Resistor
Brake unit
VFDB
XXXX
B2
22
Parallel Serie
M1 M2
Temperature switch
7
8
9
10
15
xln (A)
/