Terminal Counting Value Attained (Return To 0); Preliminary Counting Value Attained (Not Return To 0); Digital Output Gain(Dfm); Desired Frequency Attained 1, 2 - Delta C2000 series User Manual

Classical field oriented control ac motor drive
Hide thumbs Also See for C2000 series:
Table of Contents

Advertisement

Bit setting
bit15 bit14 bit13 bit12 bit11 bit10
MO20 MO19 MO18 MO17 MO16 MO15 MO14 MO13 MO12 MO11 MO10 MO2 MO1 Reserved RY2 RY1

Terminal Counting Value Attained (return to 0)

Settings
 The counter trigger can be set by the multi-function terminal MI6 (set Pr.02-06 to 23). Upon
completion of counting, the specified output terminal will be activated (Pr.02-13~02-14, Pr.02-36,
02-37 is set to 18). Pr.02-19 can't be set to 0.
 When the display shows c5555, the drive has counted 5,555 times. If display shows c5555, it
means that real counter value is between 55,550 to 55,559.

Preliminary Counting Value Attained (not return to 0)

Settings
 When the counter value counts from 1 and reaches this value, the corresponding multi-function
output terminal will be activated, provided one of Pr. 02-13, 02-14, 02-36, 02-37 set to 17
(Preliminary Count Value Setting). This parameter can be used for the end of the counting to make
the drive runs from the low speed to stop.
Di spl ay va lu e
[00 -04 =0 1]
[02-06=23]
TRG
Counter Trigger
( ou tpu t sig na l)
P re li min ar y Cou nte r V al ue
RY 1 P r.0 2- 13 =17
Te rmi na l Co un ter Va lu e
RY 2 P r.0 2- 14 =18
Digital Output Gain(DFM)
Settings
 It is used to set the signal for the digital output terminals (DFM-DCM) and digital frequency output
(pulse X work period=50%). Output pulse per second = output frequency X Pr.02-21.
Desired Frequency Attained 1
Settings
The Width of the Desired Frequency Attained 1
Settings
Desired Frequency Attained 2
bit9
0~65535
0~65535
02 -13, 02- 14, 0 2-3 6, 02 -37
02 -14=1 7
1~166
0.00~600.00Hz
0.00~600.00Hz
Chapter 12 Description of Parameter SettingsC2000 Series
bit8
bit7
bit6
bit5
02 -20=3
02 -19=5
12-50
bit4
bit3
bit2
bit1 bit0
Factory Setting: 0
Factory Setting: 0
1.0msec
1.0msec
Th e wi dth of tr ig ge r si gn al
Factory Setting: 1
Factory Setting: 60.00/50.00
Factory Setting: 2.00
Factory Setting: 60.00/50.00