Basic Registers

BR#
R/W
Model name
#0
R
Firmware
#1
R
version
Release date of
#2
R
the version
#11
R/W
Modbus Timeout Pre-defined setting: 500 (ms)
#13
R/W
Keep Alive Time Pre-defined setting: 30 (s)
LED Indicator & Troubleshooting
LED Indicators
LED
Status
POWER
Green
LINK
Green
Troubleshooting
Abnormality
POWER LED off
LINK LED off
No module found
Fail to open
CMC-MOD01
setup page
Able to open
CMC-MOD01
setup page but fail
to utilize webpage
monitoring
Content
Set up by the system; read only. The model code of
CMC-MOD01=H'0203
Displaying the current firmware version in hex, e.g. H'0100 indicates the
firmware version V1.00.
Displaying the data in decimal form. 10,000s digit and 1,000s digit are for
"month"; 100s digit and 10s digit are for "day".
For 1 digit: 0 = morning; 1 = afternoon.
On
Power supply in normal status
Off
No power supply
On
Network connection in normal status
Flashes
Network in operation
Off
Network not connected
Cause
AC motor drive not powered
CMC-MOD01 not connected
to AC motor drive
CMC-MOD01 not connected
to network
Poor contact to RJ-45
connector
CMC-MOD01 not connected
to network
PC and CMC-MOD01 in
different networks and
blocked by network firewall.
CMC-MOD01 not connected
to network
Incorrect communication
setting in DCISoft
PC and CMC-MOD01 in
different networks and
blocked by network firewall.
Incorrect network setting in
CMC-MOD01
Chapter 8 Optional Cards C2000 Series
Explanation
Indication
How to correct it?
Check if AC motor drive is powered, and if the
power supply is normal.
Make sure CMC-MOD01 is connected to AC motor
drive.
Make sure the network cable is correctly connected
to network.
Make sure RJ-45 connector is connected to
Ethernet port.
Make sure CMC-MOD01 is connected to network.
Search by IP or set up relevant settings by AC
motor drive keypad.
Make sure CMC-MOD01 is connected to the
network.
Make sure the communication setting in DCISoft is
set to Ethernet.
Conduct the setup by AC motor drive keypad.
Check if the network setting for CMC-MOD01 is
correct. For the Intranet setting in your company,
please consult your IT staff. For the Internet setting
in your home, please refer to the network setting
instruction provided by your ISP.
8-17
How to correct it?
--
Check the power supply
--
--
Check if the network cable is
connected