Electronic Thermal Relay Selection (Motor 1)
Electronic Thermal Relay Selection (Motor 2)
Settings
 It is used to prevent self-cooled motor overheats under low speed. User can use electronic thermal
relay to limit driver's output power.
Electronic Thermal Characteristic for Motor 1
Electronic Thermal Characteristic for Motor 2
Settings
 The parameter is set by the 150% of motor rated current and the setting of Pr.06-14 and Pr.06-28 to
prevent the motor damaged from overheating. When it reaches the setting, it will display
"EoL1/EoL2" and the motor will be in free running.

Heat Sink Over-heat (OH) Warning

Settings
 Pr.06-15 sets the heatsink temperature level of the drive. The drive will output an overheating
warning when the temperature exceeds the setting of Pr.06-15. If the setting of Pr.06-15 is higher
than the default setting of the drive, the drive will use the default setting level for warning output.
Capacitor (CAP) overheating level is set by the drive's default setting, it can not be adjusted.
Over-heating Level (℃)
Model
VFD007C23A/E
VFD015C23A/E
VFD022C23A/E
VFD037C23A/E
VFD055C23A/E
VFD075C23A/E
Chapter 12 Description of Parameter SettingsC2000 Series
0: Constant torque output motor
1: Variable torque output motor
2: Disable
30.0~600.0 sec
Operation
time(min)
5
4
3
2
1
0 20 40 60 80100120140160180200
0.0~110.0℃
IGBT OH1
CAP OH 2
100
90
100
90
100
90
100
95
100
75
100
75
12-
60Hz or more
50Hz
10Hz
5Hz
Load
factor (%)
Over-heating Level (℃)
Model
VFD055C43A/E
VFD075C43A/E
VFD110C43A/E
VFD150C43A/E
VFD185C43A/E
VFD220C43A/E
104
Factory Setting: 2
Factory Setting: 60.0
s
Factory Setting: 85.0
IGBT OH1
CAP OH 2
100
95
95
75
95
75
95
75
95
80
95
80