Digital Input/Output Parameter; 2-Wire/3-Wire Operation Control; Multi-Function Input Command 1-8 (Mi1-Mi8); Input Terminal Of I/O Extension Card (Mi10-Mi12) - Delta C2000 series User Manual

Classical field oriented control ac motor drive
Hide thumbs Also See for C2000 series:
Table of Contents

Advertisement

02 Digital Input/Output Parameter

2-wire/3-wire Operation Control

Settings
 It is used to set the operation control method:
Pr.02-00
2-wire mode 1
FWD/STOP
REV/STOP
2-wire mode 2
RUN/STOP
REV/FWD
3-wire operation control
Multi-function Input Command 1 (MI1) (MI1= STOP command when in 3-wire operation
control)
Multi-function Input Command 2 (MI2)
Multi-function Input Command 3 (MI3)
Multi-function Input Command 4 (MI4)
Multi-function Input Command 5 (MI5)
Multi-function Input Command 6 (MI6)
Multi-function Input Command 7 (MI7)
Multi-function Input Command 8 (MI8)
Input terminal of I/O extension card (MI10)
Input terminal of I/O extension card (MI11)
Input terminal of I/O extension card (MI12)
0: 2 wire mode 1
1: 2 wire mode 2
2: 3 wire mode
0
1
2
Chapter 12 Description of Parameter SettingsC2000 Series
 This parameter can be set during operation.
Control Circuits of the External Terminal
FWD/ STOP
REV/STOP
FWD: ("OPEN ": STOP)
RUN /STOP
REV:("OPEN": F WD)
FWD/ REV
DCM
F WD "CLOSE": RUN
RUN
STOP
MI1 "OPEN":STOP
REV/F WD "OPEN": F WD
REV/FWD
DC M
12-33
Factory Setting: 0
FWD: ("OPEN":STOP)
("CL OSE":FWD)
REV:("OPEN": ST OP)
("C LOSE": REV)
DCM
VFD -C
("CLOSE":RUN )
("C LOSE": REV)
VFD -C
"CLOSE": REV
VF D- C
Factory Setting: 1
Factory Setting: 2
Factory Setting: 3
Factory Setting: 4

Advertisement

Table of Contents
loading

Table of Contents