Chapter 8 Optional Cards C2000 Series

8-3 EMC-D42A

MI10~ MI13
I/O Extension
Card
MO10~MO11

8-4 EMC-D611A

I/O Extension
Card
MI10~ MI15

8-5 EMC-R6AA

Relay Extension
RA10~RA15
Card
RC10~RC15
Terminals
Common for Multi-function input terminals
COM
Select SINK (NPN) /SOURCE (PNP) in J1 jumper / external power
supply
Refer to parameters 02-26~02-29 to program the multi-function
inputs MI10~MI13.
Internal power is applied from terminal E24: +24Vdc±5% 200mA,
5W
External power +24VDC: max. voltage 30VDC, min. voltage
19VDC, 30W
ON: the activation current is 6.5mA
OFF: leakage current tolerance is 10μA
Multi-function output terminals (photocoupler)
Duty-cycle: 50%
Max. output frequency: 100Hz
Max. current: 50mA
Max. voltage: 48Vdc
Common for multi-function output terminals MO10,
MO11(photocoupler)
MXM
Max 48VDC 50mA
Terminals
AC
AC power Common for multi-function input terminal (Neutral)
Refer to Pr. 02.26~ Pr. 02.31 for multi-function input selection
Input voltage: 100~130VAC
Input frequency: 47~63Hz
Input impedance: 27Kohm
Terminal response time:
ON: 10ms
OFF: 20ms
Terminals
Refer to Pr. 02.36~ Pr. 02.41 for multi-function input selection
Resistive load:
5A(N.O.) /250Vac
5A(N.O.) /30Vdc
Inductive load (COSPHI 0.4)
2.0A(N.O.) /250Vac
2.0A(N.O.) /30Vdc
It is used to output each monitor signal, such as drive is in
operation, frequency attained or overload indication.
Descriptions
Descriptions
Descriptions