Delta C2000 series User Manual page 407

Classical field oriented control ac motor drive
Hide thumbs Also See for C2000 series:
Table of Contents

Advertisement

ID*
Fault Name
Fault
15
OrP
Phase lacked
Fault
16
oH1
IGBT over heat
Fault
17
oH2
Heat Sink oH
Fault
18
tH1o
Thermo 1 open
Fault
19
tH2o
Thermo 2 open
Fault
21
oL
Over load
Fault
22
EoL1
Thermal relay 1
Fault
23
EoL2
Thermal relay 2
Fault Descriptions
Phase Loss
IGBT overheating
IGBT temperature exceeds
protection level
Heatsink overheating
Capacitance temperature
exceeds cause heatsink
overheating.
IGBT Hardware Error
Capacitor Hardware Error
Overload
The AC motor drive
detects excessive drive
output current.
Electronics thermal relay 1
protection
Electronics thermal relay
2 protection
Chapter 14 Fault Codes and Descriptions C2000 Series
Corrective Actions
Check Power Source Input if all 3 input phases are
connected without loose contacts.
For models 40hp and above, please check if the fuse
for the AC input circuit is blown.
1.
Ensure that the ambient temperature falls within
the specified temperature range.
2.
Make sure that the ventilation holes are not
obstructed.
3.
Remove any foreign objects from the heatsinks
and check for possible dirty heat sink fins.
4.
Check the fan and clean it.
5.
Provide enough spacing for adequate ventilation.
1.
Ensure that the ambient temperature falls within
the specified temperature range.
2.
Make sure heat sink is not obstructed. Check if
the fan is operating
3.
Check if there is enough ventilation clearance for
AC motor drive.
Return to the factory
Return to the factory
1.
Check if the motor is overloaded.
2.
Take the next higher power AC motor drive
model.
1. Check the setting of electronics thermal relay
(Pr.06-14)
Take the next higher power AC motor drive model
1. Check the setting of electronics thermal relay
(Pr.06-28)
2. Take the next higher power AC motor drive model
14-3

Advertisement