Rated Power Of Induction Motor 1(Kw); Rated Speed Of Induction Motor 1 (Rpm); Pole Number Of Induction Motor 1; No-Load Current Of Induction Motor 1 (A) - Delta C2000 series User Manual

Classical field oriented control ac motor drive
Hide thumbs Also See for C2000 series:
Table of Contents

Advertisement

Rated Power of Induction Motor 1(kW)

Settings
 It is used to set rated power of the motor 1. The factory setting is the power of the drive.

Rated Speed of Induction Motor 1 (rpm)

Settings
 It is used to set the rated speed of the motor and need to set according to the value indicated on
the motor nameplate.
 Before set up this parameter, you need to set up Pr05-04.

Pole Number of Induction Motor 1

Settings
 It is used to set the number of motor poles (must be an even number).
 Set up Pr.05-04 before you set up Pr.05-03.

No-load Current of Induction Motor 1 (A)

Settings
 The factory setting is 40% X rated current.
Stator Resistance(Rs) of Induction Motor 1
Rotor Resistance(Rr) of Induction Motor 1
Settings
Magnetizing Inductance(Lm) of Induction Motor 1
Stator inductance(Lx) of Induction Motor 1
Settings
~
Reserved
Full-load Current of Induction Motor 2(A)
Chapter 12 Description of Parameter SettingsC2000 Series
0~655.35 kW
0~65535
2~20
0 to the factory setting in Pr.05-01
0~65.535Ω
0~6553.5mH
12-
93
Factory Setting: #.##
Factory Setting:
1710(60Hz 4 poles)
1410(50Hz 4 poles)
Factory Setting: 4
Unit: Amper
Factory Setting: #.##
Factory Setting: #.###
Factory Setting: #.#
Unit: Amper
Factory Setting:#.##