Gain Of Analog Output 1, 2 (Afm1, Afm2); Analog Output 1, 2 When In Rev Direction (Afm1, Afm2) - Delta C2000 series User Manual

Classical field oriented control ac motor drive
Hide thumbs Also See for C2000 series:
Table of Contents

Advertisement

6
Power factor
7
Power
8
Output torque
9
AVI
10
ACI
11
AUI
12
q-axis current (Iq)
13
q-axis feedback value (Iq)
14
d-axis current (Id)
15
d-axis feedback value (Id)
16
q-axis voltage (Vq)
17
d-axis voltage(Vd)
18
Torque command
19
PG2 frequency command
20
Output for CANopen control
21
RS485 analog output
Analog output for
22
communication card
23
Constant voltage/current output
Gain of Analog Output 1 (AFM1)
Gain of Analog Output 2 (AFM2)
Settings
 It is used to adjust the analog voltage level (Pr.03-20) that terminal AFM outputs.
 This parameter is set the corresponding voltage of the analog output 0.
Analog Output 1 when in REV Direction (AFM1)
Analog Output 2 when in REV Direction (AFM2)
Settings
Chapter 12 Description of Parameter SettingsC2000 Series
-1.000~1.000=100%
Rated power is regarded as 100%
Full-load torque is regarded as 100%
0~10V=0~100%
0~20mA=0~100%
-10~10V=0~100%
(2.5 X rated current) is regarded as 100%
(2.5 X rated current) is regarded as 100%
(2.5 X rated current) is regarded as 100%
(2.5 X rated current) is regarded as 100%
250V (500V) =100%
250V (500V) =100%
Rated torque is regarded as 100%
Max. frequency Pr.01-00 is regarded as 100%.
For CANopen analog output
For communication output (CMC-MOD01, CMC-EIP01,
CMC-PN01, CMC-DN01)
For communication output (CMC-MOD01, CMC-EIP01,
CMC-PN01, CMC-DN01)
Pr.03-32 and Pr.03-33 controls voltage/current output
level
0~100% of Pr.03-32 corresponds to 0~10V of AFM1.
0~500.0%
0: Absolute value in REV direction
1: Output 0V in REV direction; output 0-10V in FWD direction
2: Output 5-0V in REV direction; output 5-10V in FWD direction
12-
78
Factory Setting: 100.0
Factory Setting: 100.0
Factory Setting: 0
Factory Setting: 0