Air Flow Rate For Cooling; Power Dissipation Of Ac Motor Drive - Delta C2000 series User Manual

Classical field oriented control ac motor drive
Hide thumbs Also See for C2000 series:
Table of Contents

Advertisement

Frame D VFD300C23A/E; VFD370C23A/E; VFD370C43A/E; VFD450C43A/E; VFD550C43A/E;
VFD750C43A/E
Frame E VFD450C23A/E; VFD550C23A/E; VFD750C23A/E; VFD900C43A/E; VFD1100C43A/E
Frame F VFD900C23A/E; VFD1320C43A/E; VFD1600C43A/E
Frame G VFD1850C43A; VFD2200C43A; VFD1850C43E; VFD2200C43E
Frame H VFD2800C43A; VFD3150C43A; VFD3550C43A; VFD2800C43E-1; VFD3150C43E-1;
VFD3550C43E-1;VFD2800C43E; VFD3150C43E; VFD3550C43E
NOTE
1. The minimum mounting clearances stated in the table above applies to AC motor drives frame A to D. A drive fails
to follow the minimum mounting clearances may cause the fan to malfunction and heat dissipation problem.
Model No.
External Internal
VFD007C23A
-
VFD015C23A
14
VFD022C23A
14
VFD037C23A
10
VFD055C23A
40
VFD075C23A
66
VFD110C23A
58
VFD150C23A
166
VFD185C23A
166
VFD220C23A
146
VFD300C23A/E
179
VFD370C23A/E
179
VFD450C23A/E
228
VFD550C23A/E
228
VFD750C23A/E
246
VFD900C23A/E
224
VFD007C43A/E
-
VFD015C43A/E
-
NOT E
The mounting clearances stated in the figure is for installing the drive in an
open area. To install the drive in a confined space (such as cabinet or
electric box), please follow the following three rules: (1) Keep the minimum
mounting clearances. (2) Install a ventilation equipment or an air conditioner
to keep surrounding temperature lower than operation temperature. (3)
Refer to parameter setting and set up Pr. 00-16, Pr.00-17, and Pr. 06-55.
The following table shows the heat dissipation and the required air
volume when installing a single drive in a confined space. When
installing multiple drives, the required air volume shall be multiplied
by the number the drives.
Refer to the chart (Air flow rate for cooling) for ventilation equipment
design and selection.
Refer to the chart (Power dissipation) for air conditioner design and
selection.

Air flow rate for cooling

Flow Rate (cfm)
Total
External Internal
-
-
-
14
-
14
-
10
14
54
14
80
14
73
12
178
12
178
12
158
30
209
30
209
73
301
73
301
73
319
112
336
-
-
-
-
3
Flow Rate (m
/hr)
Total
-
-
-
24
-
24
24
-
24
17
-
17
68
24
92
112
24
136
99
24
124
282
20
302
282
20
302
248
20
268
304
51
355
304
51
355
387
124
511
387
124
511
418
124
542
381
190
571
-
-
-
-
-
-
2-3
Chapter 2 InstallationC2000 Series
Power dissipation of AC motor
drive
Power Dissipation
Loss External
Internal
(Heat sink)
33
27
56
31
79
36
113
46
197
67
249
86
409
121
455
161
549
184
649
216
913
186
1091
220
1251
267
1401
308
1770
369
2304
484
33
25
45
29
Total
61
88
115
159
264
335
529
616
733
865
1099
1311
1518
1709
2139
2788