Current detection level of output phase loss
Settings
Output phase loss detection function executing time before run
Settings
During the run: Any output phase current is smaller than the level of Pr06-47 and starts to count
time to surpass Pr06-46
Before the run:
01 When performing output phase loss detection, if any output phase is smaller than the level of
Pr06-47 and starts to count time to surpass Pr06-46, that means the motor drive has an output phase
loss and the motor drive will follow the setting of Pr06-45.
02 When Pr06-48 = 0, output phase loss detection before the run is disable.
03 The setting value of Pr06-48 must be larger than the setting of Pr06-46.
Reserved
Reserved
Reserved
Reserved
Treatment for the detected Input Phase Loss (OrP)
Settings
Over ripple protection
When the DC BUS ripple is bigger than protection level, drive will trip up OrP and depending on
how the parameter 06-53 is set to stop.
Reserved
Derating Protection
Settings
Chapter 12 Description of Parameter SettingsC2000 Series
0.00~655.35%
0.000~65.535 sec
0: warn, ramp to stop
1: warn, coast to stop
0: constant rated current and limit carrier wave by load current and
temperature
1: constant carrier frequency and limit load current by setting carrier wave
2: constant rated current(same as setting 0), but close current limit
12-
113
Factory Setting:1.00
Factory Setting:0.000
Factory Setting: 0
Factory Setting: 0