Fault Code; Address Of Communication Card; Setting Of Devicenet Speed; Other Setting Of Devicenet Speed - Delta C2000 series User Manual

Classical field oriented control ac motor drive
Hide thumbs Also See for C2000 series:
Table of Contents

Advertisement

Chapter 12 Description of Parameter SettingsC2000 Series
Profibus: ID number of a communication card. Each Profibus selling in the market must apply for
an ID number at the Profibus International to be a unique product.

Fault Code

Settings
 For more information about Fault codes, refer to Pr. 06-17~06-22 and Chapter 14.
~
Reserved

Address of Communication Card

Settings
Setting of DeviceNet Speed (according to Pr.09-72)
Settings

Other Setting of DeviceNet Speed

Settings
 It needs to use with Pr.09-71.
 Setting 0: the baud rate can only be set to 0, 1, 2 or 3.
 Setting 1: setting of DeviceNet baud rate can be the same as CANopen (setting 0-8).
Read only
DeviceNet: 0-63
Profibus-DP: 1-125
Standard DeviceNet:
0: 125Kbps
1: 250Kbps
2: 500Kbps
Non standard DeviceNet: (Delta only)
0: 10Kbps
1: 20Kbps
2: 50Kbps
3: 100Kbps
4: 125Kbps
5: 250Kbps
6: 500Kbps
7: 800Kbps
8: 1Mbps
0: Disable
1: Enable
160
Factory Setting: ##
Factory Setting: 1
Factory Setting: 2
Factory Setting: 0