Chapter 12 Description of Parameter SettingsC2000 Series
Encoder Slip Range
Settings
Detection Time of Encoder Slip
Settings
Treatment for Encoder Stall and Slip Error
Settings
When the value of (rotation speed – motor frequency) exceeds Pr.10-13 setting, detection time
exceeds Pr.10-14; it will start to accumulate time. If detection time exceeds Pr.10-14, the encoder
feedback signal error will occur. Refer to Pr.10-15 encoder stall and slip error treatment.
Pulse Input Type Setting (PG card: PG2)
Settings
When this setting is different from Pr.10-02 setting and the source of the frequency command is
pulse input (Pr.00-20 is set to 4 or 5), it may have 4 times frequency problem.
Example: Assume that Pr.10-01=1024, Pr.10-02=1, Pr.10-16=3, Pr.00-20=5, MI=37 and ON, it
0~50%
0: Disable
0.0~10.0 sec
0: Warn and keep operation
1: Warn and ramp to stop
2: Warn and coast to stop
0: Disable
1: Phase A leads in a forward run command and phase B leads in a reverse
run command
FW D
A
B
2: Phase B leads in a forward run command and phase A leads in a reverse
run command
FW D
A
B
3: Phase A is a pulse input and phase B is a direction input. (L=reverse
direction, H=forward direction)
F WD
A
B
4: Phase A is a pulse input and phase B is a direction input. (L=forward
direction, H=reverse direction)
FWD
A
B
REV
REV
REV
REV
166
Factory Setting: 50
Factory Setting: 0.5
Factory Setting: 2
Factory Setting: 0