Delta C2000 series User Manual page 618

Classical field oriented control ac motor drive
Hide thumbs Also See for C2000 series:
Table of Contents

Advertisement

3. Common-mode noise is coupled via the power cable to other power systems then the cable of such a
power system is coupled to the transmission system, as shown in Figure 3.
4. The common-mode noise of an unshielded power cable is transmitted to the ground via the stray
capacitance. Since both shielded wire and unshielded wire are connected to a common ground, other
systems can be interfered with by the common-mode noise that is transmitted from the ground back
to the system via the shield. See Figure 4.
5. When excessive pulse modulated currents pass through an un-grounded AC drive cable, it acts as an
antenna and creates radiated interference.
Unshielded cable
Noise
Power
supply
Unshielded cable
Noise
Send
Noise
Send
Cstray
System
Cable
Ground
Cstray
Ground
Unshielded cable
Cstray
Cstray
Ground
3
Receive
Load
Receive
Load