Delta C2000 series User Manual page 473

Classical field oriented control ac motor drive
Hide thumbs Also See for C2000 series:
Table of Contents

Advertisement

Special D
D1021
Output current (####.#A)
The ID of the extension card:
0: no card
D1022
1: Relay Card( 6 out )
2: I/O Card ( 4 in 2 out )
3~7: Reserved
The ID of the extension card:
0: no card
1: DeviceNet Slave
2: Profibus-DP Slave
D1023
3: CANopen Slave
4: Modbus-TCP Slave
5: EtherNet/IP Slave
6~8: Reserved
D1024
~
Reserved
D1026
D1027
Frequency command of the PID control
D1028
The responsive value of AUI AVI (analog voltage input) (0.00~100.00%) Read only
D1029
The responsive value of AUI ACI (analog current input) (0.0~100.00%)
D1030
The corresponding value for AUI (-100.0~100.00%)
D1031
~
Reserved
D1035
D1036
AC motor drive error code
D1037
AC motor drive output frequency
D1038
DC Bus voltage
D1039
Output voltage
D1040
Analog output value AFM1 (-100.00~100.00%)
D1041
~
Reserved
D1042
User defined (When Pr.00.04 is set to 28, the register data will be
D1043
displayed as C xxx)
D1044
Reserved
D1045
Analog output value AFM2 (-100.00~100.00%)
D1046
~
Reserved
D1049
Actual mode
0: Velocity mode
D1050
1: Position mode
2: Torque mode
3: Homing mode
D1051
~
Reserved
D1052
D1053
Actual torque
D1054
Present count value of MI8(L word)
D1055
Present count value of MI8 (H word)
Chapter 16 PLC Function C2000 Series
Function
16-26
Read(R)/
Write(W)
Read only
Read only
Read only
-
Read only
Read only
Read only
-
Read only
Read only
Read only
Read only
Read/Write
-
Read/Write
-
Read/Write
-
Read only
-
Read only