Start-Point For Dc Brake; Voltage Incrasing Gain; Restart After Momentary Power Loss - Delta C2000 series User Manual

Classical field oriented control ac motor drive
Hide thumbs Also See for C2000 series:
Table of Contents

Advertisement

Chapter 12 Description of Parameter SettingsC2000 Series

Start-Point for DC Brake

Settings
 This parameter determines the frequency when DC Brake will begin during deceleration. When
this setting is less than start frequency (Pr.01-09), the start-point for DC brake will start from the
min. frequency.
 DC Brake at Start-up is used for loads that may move before the AC drive starts, such as fans and
pumps. Under such circumstances, DC Brake can be used to hold the load in position before
setting it in motion.
 DC Brake at stop is used to shorten the stopping time and also to hold a stopped load in position,
such as crane or cutting machine.
 DC Brake at Start-up is used for loads that may move before the AC drive starts, such as fans and
pumps. Under such circumstances, DC Brake can be used to hold the load in position before
setting it in motion.
 DC Brake at stop is used to shorten the stopping time and also to hold a stopped load in position,
such as crane or cutting machine.

Voltage Incrasing Gain

Settings
 When the user is using speed tracking, adjut Pr07-05 to slow down the increasing of voltage if
there are errors such as oL or ocv.

Restart after Momentary Power Loss

Settings
 This parameter determines the operation mode when the AC motor drive restarts from a
momentary power loss.
 The power connected to the drive may power off momentarily due to many reasons. This function
allows the drive to keep outputting after power is on again after power off and won't cause drive
stops.
0.00~600.00Hz
Output frequen cy
01-09
Minimum
out put
frequen cy
Run /Stop
1~200%
0: Stop operation
1: Speed search for last frequency command
2: Speed search for the minimum output frequency
DC Brak Time
07-04
during St opping
Start-point for
DC brake
time during
stopping
OFF
ON
DC Brake Time
124
Factory Setting: 0.00
Time
Factory Setting: 100
Factory Setting: 0