Wiring Diagram For Frame D And Frames Above - Delta C2000 series User Manual

Classical field oriented control ac motor drive
Hide thumbs Also See for C2000 series:
Table of Contents

Advertisement

* It provides 3-phase power
Fuse/NFB( No Fuse Breaker)
R(L1)
S(L2)
T(L3)
Factory setting: NPN (SINK) Mode
Please refer to
FWD/STOP
Figure 2 for wiring
REV/STOP
of NPN mode and
Multi-step 1
PNP mode.
Multi-step 2
Multi-step 3
Factory
Multi-step 4
setting
N/A
N/A
N/A
N/A
Digital Signal Common
NOTE
* MI8 can input 33kHz
* Do NOT apply the mains voltage directly
to above terminals.
5K
Analog Signal Common
Modbus RS-485
CAN BUS
Pin 1~2, 7, 8: reserved
Pin 3, 6:SGND
Pin 4:SG-
Pin 5:SG+
Main circuit (power) terminals
Please refer to figure 3
R(L1)
S(L2)
T(L3)
SA
MC
RB 1
RC 1
ON
OFF
MC
+24V
COM
FWD
REV
MI1
MI2
MI3
MI4
MI5
MI6
MI7
MI8
DCM
pulses
S1
power removal safety function
for emergency stop
Digital Signal Common
SCM
+10V
3
0~10 V/ 0~20mA
AVI
2
1
4~20 mA/0~1 0V
ACI
-10~+10 V
AUI
ACM
-10V
-10V /20mA
SGND
8 1
SG+
SG-
-/DC-
+/D C+
U(T1)
V(T2)
W(T3)
RA1
RB1
RC1
RA2
RB2
RC2
Option
Slot 1
Option
Slot 2
8 1
Option
Slot 3
Control terminals
4-3
Chapter 4 WiringC2000 Series
Motor
IM
3~
Multi-function output terminals
250 Vac/5A (N.O.)
250 Vac/3A (N.C.)
250 Vac/2A (N.O.)
Estimate at COS (0.4 )
250 Vac/1.2A (N.C.)
Estimate at COS (0.4 )
30V dc/5A (N.O.)
30V dc/3A (N.C.)
Multi-function output
DFM
frequency terminals
30V30mA 100kHz
DCM
Multi-function output
MO1
frequency terminals
48V/50mA
Multi-function output
MO2
frequency terminals
48V/50mA
Multi-function
MCM
Photocoupler Output
IO exte nsion ca rd
PG exten sion ca rd
IO &RELA Y
exten sion ca rd
Shielded leads & Cable

Advertisement

Table of Contents
loading

Table of Contents