09 Communication Parameters
COM1 Communication Address
Settings
If the AC motor drive is controlled by RS-485 serial communication, the communication address
for this drive must be set via this parameter and each AC motor drive's communication address
must be different.
COM1 Transmission Speed
Settings
This parameter is for set up the RS485 communication transmission speed.
COM1 Transmission Fault Treatment
Settings
This parameter is set to how to react if transmission errors occur.
COM1 Time-out Detection
Settings
It is used to set the communication transmission time-out..
COM1 Communication Protocol
Settings
When us ing communication devi ces,
connects AC dr ive with P C by us ing
Delta IFD6530 or IFD6500.
1~254
4.8~115.2Kbits/s
0: Warn and keep operation
1: Warn and ramp to stop
2: Warn and coast to stop
3: No warning and continue operation
0.0~100.0 sec
0.0: Disable
1: 7, N, 2 for ASCII
2: 7, E, 1 for ASCII
3: 7, O, 1 for ASCII
4: 7, E, 2 for ASCII
5: 7, O, 2 for ASCII
6: 8, N, 1 for ASCII
7: 8, N, 2 for ASCII
8: 8, E, 1 for ASCII
9: 8, O, 1 for ASCII
Chapter 12 Description of Parameter SettingsC2000 Series
The parameter can be set during the operation.
8
1
Modbus RS- 485
Pin 1~2,7,8: Reserv ed
Pin 3, 6: GND
Pin 4: SG-
Pin 5: SG+
RS-485
145
Factory Setting: 1
Factory Setting: 9.6
Factory Setting: 3
Factory Setting: 0.0
Factory Setting: 1