Multi-Function Output Setting - Delta C2000 series User Manual

Classical field oriented control ac motor drive
Hide thumbs Also See for C2000 series:
Table of Contents

Advertisement

Settings
Functions
52
Output for RS-485
53~62 Reserved
Example: Crane Application
Multi-function output MO=42
It is recommended to be used with Dwell function as shown in the following:
Multi-function output MO=42
(Active when Fcmd>= Pr02-34,
output current > Pr02-33,
time>Pr02-32)

Multi-function Output Setting

Settings
 The setting of this parameter is in hexadecimal.
 This parameter is set via bit setting. If a bit is 1, the corresponding output acts in the opposite way.
Example:
If Pr02-13=1 and Pr02-18=0, Relay 1 is ON when the drive runs and is open when the drive is
stopped.
If Pr02-13=1 and Pr02-18=1, Relay 1 is open when the drive runs and is closed when the drive is
stopped.
MO6
MO7
MO8
For RS-485 output
Output
Frequency
Freq. Command>=Pr02-34
& output current >= Pr02-33
0000h~FFFFh(0:N.O. ; 1:N.C.)
Chapter 12 Description of Parameter SettingsC2000 Series
Descriptions
P2-21 = 51
RW
P2-22 = 51
RW
P2-23 = 51
RW
02-32
12-49
The bit 8 2640
The bit 9 2640
The bit 10 2640
Freq. command< Pr02-58
or output current < Pr02-57
Factory Setting: 0000