Emergency Error Codes; Table 75 Event Qualifier; Table 76 Emergency Error Codes - WAGO 765-1205/100-000 Product Manual

8-channel digital input/output; ethercat; 24 v dc; 2.0 a; 8 × m8 connection
Table of Contents

Advertisement

765-1205/100-000
Parame-
ter
Parame-
ter 2
Flags
Parame-
ter 2
Parame-
ter 3
Flags
Parame-
ter 3
Bit
Bits 6–7
Bits 4–5
Bit 3
Bits 0–2

11.2.1.9 Emergency Error Codes

The following emergency error codes are defined in the EtherCAT specification:
Emergency Error Code (hex)
00xx
10xx
20xx
21xx
22xx
23xx
30xx
31xx
32xx
Product manual | Version: 2.0.0
8DIO FLD EC DC 24V 2.0A
Data
Description
Type
UINT16
Describes the type of parameter 2
Bits 12–15 = 0
UINT8
Event Code
UINT16
Describes the type of parameter 3
Bits 12–15 = 0
UINT8
Event Qualifier
Name
Mode
Type
Source
Instance
Description
Error Reset or No Error
Generic Error
Current
Current, device input side
Current inside the device
Current, device output side
Voltage
Mains Voltage
Voltage inside the device
Bits 0–11 = data type index of the data type of parameter 2
0x0007: UINT32
The corresponding text parameters and formats are de-
scribed in document ETG.2000.
Bits 0–11 = data type index of the data type of parameter 3
0x0005: UINT8
The corresponding text parameters and formats are de-
scribed in document ETG.2000.
Description
0: reserved
1: single event
2: event disappears
3: event appears
0: reserved
1: notification
2: warning
3: error
0: device (remote)
1: master/port
0: unknown
1–3: reserved
4: application
5–7: reserved
Table 76: Emergency Error Codes
Diagnostics
Table 75: Event Qualifier
107

Advertisement

Table of Contents
loading

Table of Contents