Diagnostics Via Ethernet/Ip; Error Codes (Cip Status) - WAGO 765-1505/100-000 Product Manual

I/o system field 8-channel digital input/output; ethernet/ip; 24 v dc; 2.0 a; 8 × m8 connection
Table of Contents

Advertisement

Diagnostics
LED State
Flickering
(load-dependent)
Bluetooth
The Bluetooth
tion status.
LED
BT
Port Status
LEDs 0 (port X01), 1 (port X02), ..., 7 (port X08) indicate the status of the digital input/out-
put module.
LED
0, 1, 2, ...
Port Status
(pin 4)

11.2 Diagnostics via EtherNet/IP

The module contains the event log object with information on IO-Link events. The con-
troller can read the attributes of the event log object in order to get the "Event Qualifier"
and "Event Code" of an IO-Link event. A CIP instance is assigned to each IO-Link port.
The object's attributes are described in Event Log Object 65 (0x41).

11.2.1 Error Codes (CIP Status)

CIP Status
0 (0x00)
1 (0x01)
2 (0x02)
3 (0x03)
104
Product manual | Version: 2.0.0
8DIO FLD EI DC 24V 2.0A
Definition
The LED indicates high ETHERNET activity by switching on and off at a frequency of
10 Hz:
"On" for 50 ms and then "Off" for 50 ms.
The LED indicates low ETHERNET activity by switching on and off at irregular intervals.
®
Status
®
LED is integrated into the Bluetooth
Color
Duo LED, blue/red
Blue
Off
Color
Duo LED, yellow/red (yellow = simultaneously red and green)
yellow
Off
red
red
Description
Success
The addressed object has executed the service successfully.
Connection error
A connection-specific service has failed. The error may have occurred anywhere
along the connection path.
Resource not available
Some resources the object needs in order to execute the service are unavailable.
Invalid parameter value
See CIP status 32 (0x20).
®
antenna and indicates the connec-
State
Description
On
Bluetooth
Off
Bluetooth
State
Description
On
Status of digital input/output: 1
Off
Status of digital input/output: 0
On
Overload, short circuit (pin 4 and pin 3)
Flashing 1 Hz
Overload, sensor supply short circuit (pin 1
and pin 3)
765-1505/100-000
Table 71: LED States – Ethernet
Table 72: LED States
®
connection established
®
inactive
Table 73: Port Status
Table 74: Error Codes (CIP Status)
®

Advertisement

Table of Contents
loading

Table of Contents