Device Description
3.2.2
Power Jumper Contacts/Field Supply
Power from SELV/PELV power supply only!
All field signals and field supplies connected to this XTR I/O module
(750-1516/040-000) must be powered from SELV/PELV power supply(s)!
Risk of injury due to sharp-edged blade contacts!
The blade contacts are sharp-edged. Handle the I/O module carefully to prevent
injury. Do not touch the blade contacts.
The I/O module 750-1516/040-000 has 2 self-cleaning power jumper contacts
that supply and transmit power for the field side. The contacts on the left side of
the I/O module are designed as blade contacts and those on the right side as
spring contacts.
Figure 3: Power Jumper Contacts
Table 4: Legend for Figure "Power Jumper Contacts"
Contact
1
2
3
4
Manual
Version 1.0.0
750-1516/040-000 8DO 24 VDC 0.5A LSS 2-wire XTR
Type
Function
Spring contact Potential transmission (U
Spring contact Potential transmission (0 V) for field supply
Blade contact
Potential feed-in (0 V) for field supply
Blade contact
Potential feed-in (U
WAGO I/O System 750 XTR
) for field supply
v
) for field supply
v