Power Jumper Contacts/Field Supply; Figure 3: Power Jumper Contacts; Table 6: Legend For Figure "Power Jumper Contacts - WAGO 753-482 Manual

2ai 4-20ma 12 bit s.e. hart 2-channel analog input; 4-20 ma; hart; single-ended (s.e.) for wago i/o system 750
Table of Contents

Advertisement

WAGO I/O System 750
753-482 2AI 4-20mA 12 Bit S.E. HART
3.2.2

Power Jumper Contacts/Field Supply

Risk of injury due to sharp-edged blade contacts!
The blade contacts are sharp-edged. Handle the I/O module carefully to prevent
injury. Do not touch the blade contacts.
The I/O module 753-482 has 2 self-cleaning power jumper contacts that supply
and transmit power for the field side. The contacts on the left side of the I/O
module are designed as blade contacts and those on the right side as spring
contacts.

Figure 3: Power Jumper Contacts

Table 6: Legend for Figure "Power Jumper Contacts"

Contact
1
2
3
4
Do not exceed maximum values via power contacts!
The maximum current that can flow through the power jumper contacts is 10 A.
The power jumper contacts can be damaged and the permissible operating
temperature can be exceeded by higher current values.
When configuring the system, do not exceed the permissible maximum current
value. If there is a higher power requirement, you must use an additional supply
module to provide the field voltage.
Type
Function
Spring contact Potential transmission (U
Spring contact Potential transmission (0 V) for field supply
Blade contact
Potential feed-in (0 V) for field supply
Blade contact
Potential feed-in (U
Device Description
) for field supply
v
) for field supply
v
Version 1.2.0