Note:
An actual value sensing clock cycle (p9511) that is set too low, can sporadically mean that safety messages
C01711/C30711 are output with message value 1020 or 1021.
For fault value = 108:
- set a suitable actual value sensing clock cycle in p9511.
- if the DP clock cycle is used as the actual value sensing clock cycle for operation with isochronous PROFIBUS
(p9511 = 0), then a suitable DP clock cycle must be configured. This must be set to less than 8 ms. If this is not
possible, then p9511 must be set to the required actual value sensing clock cycle (< 8 ms).
- For SIMOTION D410-2, a suitable multiple of the DP clock cycle (e.g. 1, 2, 3, 4, 5, 6, 8, 10) must be parameterized.
Otherwise, the clock cycle must be set to less than 8 ms.
For fault value = 109:
- set the actual value sensing clock cycle in p9511 to the same value as the current controller clock cycle (p0115[0]).
- SINAMICS S110: set the actual value sensing clock cycle to p9511 = 250 µs.
For fault value = 110:
- set the actual value sensing clock cycle in p9511 to 2 ms or higher.
For fault value = 111:
- set the monitoring clock cycle in p9500 as an integer multiple of the sampling time of the current controller
(p0115[0]).
For fault value = 112:
- set the actual value sensing clock cycle p9511 to the required value (not equal to zero).
For fault value = 200, 201:
- increase the current controller sampling time (p0115[0]).
- if required, reduce the number of components connected to the corresponding DRIVE-CLiQ line, or distribute the
components across several DRIVE-CLiQ sockets.
For fault value = 202:
- set the current controller sampling time to a sensible value (p0115[0]).
Note:
CU: Control Unit
MM: Motor Module
SI: Safety Integrated
F01653
SI P1 (CU): PROFIBUS/PROFINET configuration error
Message value:
%1
Message class:
Error in the parameterization / configuration / commissioning procedure (18)
Drive object:
VECTOR_G
Component:
None
Reaction:
NONE (OFF1, OFF2, OFF3)
Acknowledge:
IMMEDIATELY (POWER ON)
Cause:
There is a PROFIBUS/PROFINET configuration error for using Safety Integrated monitoring functions with a higher-
level control (SINUMERIK or F-PLC).
Note:
For safety functions that have been enabled, this fault results in a STOP A that cannot be acknowledged.
Fault value (r0949, interpret decimal):
200: A safety slot for receive data from the control has not been configured.
210, 220: The configured safety slot for the receive data from the control has an unknown format.
230: The configured safety slot for the receive data from the F-PLC has the incorrect length.
231: The configured safety slot for the receive data from the F-PLC has the incorrect length.
240: The configured safety slot for the receive data from the SINUMERIK has the incorrect length.
250: A PROFIsafe slot is configured in the higher-level F control, however PROFIsafe is not enabled in the drive.
300: A safety slot for the send data to the control has not been configured.
310, 320: The configured safety slot for the send data to the control has an unknown format.
330: The configured safety slot for the send data to the F-PLC has the incorrect length.
331: The configured safety slot for the send data to the F-PLC has the incorrect length.
340: The configured safety slot for the send data to the SINUMERIK has the incorrect length.
SINAMICS G130/G150
List Manual (LH2), 07/2016, A5E03263479A
Propagation:
GLOBAL
4 Faults and alarms
4.2 List of faults and alarms
1439