F01912 (N, A)
PB/PN: clock cycle synchronous operation sign-of-life failure
Message value:
-
Message class:
Communication error to the higher-level control system (9)
Drive object:
B_INF, ENC, VECTOR_G
Component:
None
Reaction:
Vector: OFF1 (OFF3)
Infeed: OFF1
Acknowledge:
IMMEDIATELY
Cause:
The maximum permissible number of errors in the controller sign-of-life (clock synchronous operation) has been
exceeded in cyclic operation.
Remedy:
- physically check the bus (cables, connectors, terminating resistor, shielding, etc.).
- correct the interconnection of the controller sign-of-life (p2045).
- check whether the controller correctly sends the sign-of-life (e.g. create a trace with STW2.12 ... STW2.15 and
trigger signal ZSW1.3).
- check the permissible telegram failure rate (p0925).
- check the bus and controller for utilization level (e.g. bus cycle time Tdp was set too short).
Note:
PB: PROFIBUS
PN: PROFINET
Reaction upon N:
NONE
Acknowl. upon N:
NONE
Reaction upon A:
NONE
Acknowl. upon A:
NONE
A01920 (F)
PROFIBUS: Interruption cyclic connection
Message value:
-
Message class:
Communication error to the higher-level control system (9)
Drive object:
All objects
Component:
None
Reaction:
NONE
Acknowledge:
NONE
Cause:
The cyclic connection to the PROFIBUS master is interrupted.
Remedy:
Establish the PROFIBUS connection and activate the PROFIBUS master in the cyclic mode.
Note:
If there is no communication to a higher-level control system, then p2030 should be set = 0 to suppress this
message.
See also: p2030 (Field bus int protocol selection)
Reaction upon F:
NONE (OFF1)
Acknowl. upon F:
IMMEDIATELY
A01921 (F)
PROFIBUS: Receive setpoints after To
Message value:
-
Message class:
Communication error to the higher-level control system (9)
Drive object:
All objects
Component:
None
Reaction:
NONE
Acknowledge:
NONE
Cause:
Output data of PROFIBUS master (setpoints) received at the incorrect instant in time within the PROFIBUS clock
cycle.
Remedy:
- check bus configuration.
- check parameters for clock cycle synchronization (ensure To > Tdx).
SINAMICS G130/G150
List Manual (LH2), 07/2016, A5E03263479A
Propagation:
LOCAL
Propagation:
LOCAL
Propagation:
LOCAL
4 Faults and alarms
4.2 List of faults and alarms
1491

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

SinamicsG150

Table of Contents