4 Faults and alarms
4.2 List of faults and alarms
F01664
SI P1 (CU): No automatic firmware update
Message value:
%1
Message class:
Error in the parameterization / configuration / commissioning procedure (18)
Drive object:
VECTOR_G
Component:
None
Reaction:
OFF2
Acknowledge:
IMMEDIATELY (POWER ON)
Cause:
During booting, the system detected that the "Firmware update automatic" function (p7826 = 1) was not activated.
This function must be activated for automatic firmware updates/downgrades to prevent impermissible version
combinations when safety functions are enabled.
Note:
This fault does not result in a safety stop response.
See also: p7826 (Firmware update automatic)
Remedy:
When safety functions are enabled (p9501 <> 0 and/or p9601 <> 0):
1. Activate the "Firmware update automatic" function (p7826 = 1).
2. Backup the parameters (p0977 = 1) and carry out a POWER ON.
When deactivating the safety functions (p9501 = 0, p9601 = 0), the fault can be acknowledged after exiting the safety
commissioning mode.
F01665
SI P1 (CU): System is defective
Message value:
%1
Message class:
Hardware/software error (1)
Drive object:
VECTOR_G
Component:
Control Unit (CU)
Reaction:
OFF2
Acknowledge:
IMMEDIATELY
Cause:
A system defect was detected before the last boot or in the actual one. The system might have been rebooted
(reset).
Fault value (r0949, interpret hexadecimal):
200000 hex, 400000 hex, 8000yy hex (yy any):
- fault in the actual booting/operation.
800004 hex:
- parameters p9500/p9300 are, under certain circumstances, not the same. In addition, Safety message
C01711/C30711 is displayed.
Additional values:
- defect before the last time that the system booted.
Remedy:
- carry out a POWER ON (switch-off/switch-on).
- upgrade firmware to later version.
- contact Technical Support.
For fault value = 200000 hex, 400000 hex, 8000yy hex (yy any):
- ensure that the Control Unit is connected to the Power Module.
For fault value = 800004 hex:
- check that parameters p9500/p9300 are the same.
Note:
PM: Power Module
STO: Safe Torque Off
1446
Propagation:
DRIVE
Propagation:
GLOBAL
List Manual (LH2), 07/2016, A5E03263479A